Mitsubishi Electric M Series Manual page 164

Hide thumbs Also See for M Series:
Table of Contents

Advertisement

WALL-MOUNTED Inverter Heat Pump
MUZ-FD25VA
MUZ-GE25VA
MUZ-FD25VABH MUZ-GE25VAH
MUZ-FD35VA
MUZ-GE35VA
MUZ-FD35VABH MUZ-GE35VAH
Outdoor unit failure mode table
NOTE: Blinking patterns of this mode differ from the ones of "Troubleshooting check table".
w OPERATION INDICATOR lamp
POWER lamp (MSZ-FD)
Upper lamp (MSZ-GE, MSZ-HC)
Upper/Power
lamp of
OPERATION
Abnormal point
INDICATOR
(Failure mode/protection)
lamp
(Indoor unit)
OFF
None (Normal)
2-time flash
Outdoor power system
2.5 seconds
OFF
3-time flash
Discharge temperature
2.5 seconds
thermistor
OFF
Defrost thermistor
Fin temperature thermistor
P.C. board temperature
thermistor
MSZ-FD, GE
Ambient temperature
thermistor
Outdoor heat exchanger
temperature thermistor
4-time flash
Overcurrent
2.5 seconds
OFF
Compressor synchronous
abnormality (Compressor
start-up failure protection)
5-time flash
Discharge temperature
2.5 seconds
OFF
6-time flash
High pressure
2.5 seconds
OFF
7-time flash
Fin temperature/P.C. board
2.5 seconds
temperature
OFF
MSZ-FD, GE
Outdoor fan motor
8-time flash
2.5 seconds
OFF
9-time flash
Nonvolatile memory data
2.5 seconds
OFF
MUZ-GE
Power module
10-time flash
Discharge temperature
2.5 seconds
OFF
11-time flash
DC voltage
2.5 seconds
OFF
Each phase current of
compressor
12-time flash
Overcurrent Compressor
2.5 seconds
open-phase
OFF
14-time flash
Stop valve (Closed valve)
2.5 seconds
OFF
C-162
MUZ-GE42VA
MUZ-GE60VA
MUZ-GE42VAH
MUZ-GE71VA
MUZ-GE50VA
MUZ-GE50VAH
LED indication
(Outdoor P.C. board)
Overcurrent protection stop is continuously performed 3 times
within 1 minute after the compressor gets started.
1-time flash every
Thermistor shorts or opens during compressor running.
2.5 seconds
3-time flash
2.5 seconds OFF
4-time flash
2.5 seconds OFF
2-time flash
2.5 seconds OFF
11-time flash
Large current flows into intelligent power module.
2.5 seconds OFF
12-time flash
Waveform of compressor current is distorted.
2.5 seconds OFF
Temperature of discharge temperature thermistor exceeds
116°C, compressor stops.
Compressor can restart if discharge temperature thermistor
reads 100°C or less 3 minutes later.
Temperature of indoor coil thermistor exceeds 70°C in HEAT
mode. Temperature of defrost thermistor exceeds 70°C in
COOL mode.
7-time flash
Temperature of fin temperature thermistor on the inverter
2.5 seconds OFF
P.C. board exceeds 75 °C ~80 °C (MUZ-FD, MUZ-GE)/82°C
(MUZ-HC25)/83°C (MUZ-HC35), or temperature of P.C. board
temperature thermistor on the inverter P.C. board exceeds
70 °C~75 °C (MUZ-FD, MUZ-GE)/81°C (MUZ-HC25)/85°C
(MUZ-HC35).
Outdoor fan has stopped 3 times in a row within 30 seconds
after outdoor fan start-up.
5-time flash
Nonvolatile memory data cannot be read properly.
2.5 seconds OFF
6-time flash
The interphase short circuit occurs in the output of the
2.5 seconds OFF
intelligent power module (IPM).
The compressor winding shorts circuit.
Temperature of discharge temperature thermistor has been
50°C or less for 20 minutes.
8-time flash
DC voltage of inverter cannot be detected normally.
2.5 seconds OFF
9-time flash
Each phase current of compressor cannot be detected
2.5 seconds OFF
normally.
10-time flash
Large current flows into intelligent power module (IPM).
2.5 seconds OFF
The open-phase operation of compressor is detected.
The interphase short circuit occurs in the output of the
intelligent power module (IPM).
The compressor winding shorts circuit.
14-time flash
Closed valve is detected by compressor current.
2.5 seconds OFF
MUZ-HC25VA
MUZ-HC35VA
MUZ-HC35VAB
Condition
M series
Indoor/outdoor
Outdoor unit
unit failure
failure mode
mode recall
recall function
function