S series
B.3.9 CAPACITY CORRECTION RATIO CURVE PIPING LENGTH
Correction ratio of capacity according to the length of piping (cooling)
100%
99%
98%
97%
96%
95%
94%
93%
92%
91%
90%
89%
88%
87%
86%
85%
0
5
Actual length of refrigerant piping (m)
Correction ratio of capacity according to the length of piping (heating)
100%
99%
98%
97%
96%
95%
0
5
Actual length of refrigerant piping (m)
The length intended for the capacity calculation, which counts the length of refrigerant piping and
the number of bends, is called actual length.
Length of refrigerant piping (m) + ( Number of bends × 0.3 m ) = Actual length of refrigerant piping (m)
SUZ-KA25VA
SUZ-KA35VA
10
15
20
25
SUZ-KA25~71VA
10
15
20
25
SUZ-KA50VA
SUZ-KA60VA
SUZ-KA71VA
30
35
30
35
OUTDOOR UNIT
B-111