Residual Ground Fault

Residual Ground Fault
The Residual Ground Fault protection monitors the ground
current of the motor and will trip the motor if the ground cur-
rent exceeds the set threshold. The Ground Fault protection is
always active.
Protections —> Ground Fault —> Residual GF
Ground Fault
Fault
Code
Protection
Action
4
Ground Fault
Fautl Trip
(earth)
Fault
Warning
Fault Trip
Delay
Use Fault
Trip Inhibit
Fault Trip
Inhibit Run
Ú
If the C445 relay is commissioned to monitor an
AC motor, the current must be fed on all three
poles in order to prevent early tripping. DC motors
cannot be monitored.
WARNING
IMPROPER FAULT DETECTION
Residual Ground fault will not protect people from harm
caused by ground current .
Ground fault thresholds must be set to protect the
motor and related equipment .
Ground fault settings must conform to national and
local safety regulations and codes .
Failure to follow these instructions can result in death
or serious injury .
14
Safety Manual MN042004EN March 2017 www.eaton.com
Fault
Modbus
Action Units
Frame
1060
amps
C445MA2P4...
C445MA005...
C445MA032...
C445MA045...
C445MB072...
C445MC090...
C445MC136...
C445M...EXT
1061
1064
1065
%
Delay (Seconds)
Min.
Max.
Default
Min.
0.12
2.4
1
1
0.25
5
3
1
9.6
3
1
13.5
3
3
21.6
3
3
27
3
34
40.8
34
30%
50%
50%
of CT
of CT
of CT
Primary
Primary
Primary
At
powerup
0
Disable
Enable
Disable
25
100
50
0
Max.
Default Modbus
60
5
1063
2
1079
5
0
1062
0
0