Safety Considerations
Contactor Feeder Operation Mode
The Contactor Feeder operation mode accepts open/close com-
mands to control the contactor in a feeder application.
A close command will activate Output 1. An open command will
de-activate Output 1.
C445 Feedback Signal Source Selector parameter.
Input source of the feedback signals:
0 – No feedback source
1 – User interface inputs (In#2 – aux on)
2 – Base control inputs (In#2 – aux on)
3 – Fieldbus parameter
The C445 will issue a control fault when:
An Open command active and the Aux On feedback input is
true.
Current is detected after an open command.
A Close command is active and the Aux On feedback input
is false.
When the C445 experiences a fault/inhibit condition Output 1
will be de-activated to open the feeder.
Output 1 – feeder contactor coil (NO)
Outputs 2 and 3 – open for user configuration and their func-
tion can be selected by the user.
8
Safety Manual MN042004EN March 2017 www.eaton.com
General Purpose Input / Output Operation Mode
The C445 can operate as general purpose I/O providing the
user 4 discrete inputs and 3 discrete outputs that can be con-
trolled over a fieldbus network.
The inputs on the Base Control Module are not used by this
Operation Mode. All 4 inputs may be used as general purpose
inputs.
No User Interface overlays are supported by this operation
mode.
Outputs 1, 2 and 3 – open for user configuration and their func-
tion can be selected by the user.
CAUTION
When installing various motor operation mode it's
recommend to refer user manual MN042003EN.pdf for
details. The operation mode overview provided in safety
manual is at high level as quick reference.
Current Ranges Of The Overload Relays
The C445 motor management relays can be set to the rated
current of the motor using the communication cards.
The specialist personnel responsible for the installation shall
refer to the motor name plate or the approval certificate of the
motor when setting the overload relay current.
Motors with a rated current of 0.3 to 136 A can be managed
with the Measurement Module, the Base Control Module and
communication modules that are available in C445 family cata-
logue.