Eaton Power Xpert C445 Safety Manual page 9

Global motor management relay
Hide thumbs Also See for Power Xpert C445:
Table of Contents

Advertisement

DIP Switches
Output Status
Input Status
Inputs
BCM – Front View
DIP Switches: Used for node addressing and configuration
selections.
Output Status: LEDs indicate the ON/OFF status of each out-
put.
Input Status: LEDs indicate the ON/OFF status of each input.
Inputs: Four digital inputs available. Must be purchased as 24
Vdc or 120 Vac.
Test/Reset: Used to manually trip the base control module.
Also used to reset the module after a trip has occurred.
USB Port: Micro AB connector. Enables configuration upload.
Status LEDs:
Status: Indicates the trip status of the base control module.
CH1: Indicates status of modules attached to Channel 1 port
on Base Control Module (measurement module or user inter-
face).
CH2: Indicates status of modules attached to Channel 2 port
on Base Control Module (measurement module or user inter-
face).
USB: USB traffic indication.
Real Time Clock and Memory Backup Module: Optional real
time clock module. Plugs in behind the communication cards.
Provides battery backed-up fault time stamping and non-volatile
memory for configuration parameters.
Communication Modules: Optional modules to provide com-
munications.
PROFIBUS DVP0 and DVP1 (Shown)
Ethernet for ModBus/TCP and Ethernet/IP
Communication
Modules
RTC Module
Status LEDs
USB Port
Test/Reset
Relay Outputs
1 & 2
Relay
Output 3
Input Power
BCM – Bottom View
Relay Outputs 1 & 2: Two normally open outputs.
Relay Output 3: Form C NC/NO. Factory orderable as latching
or non-latching. Two options available: 120–240 Vac or 24 Vdc
RS-485: Modbus Serial terminal (factory orderable option only)
CH1 Port: Provides connection and power from the base con-
trol module to the connected module (measurement module or
user interface)
CH2 Port: Provides connection and power from the base con-
trol module to the connected module (measurement module or
user interface)
Measurement Module Basic Overview
The measurement module is a pass-through device which sam-
ples current and voltage data consumed by the system. This
data is continually transmitted back to the base control module
for analysis. Various frame sizes are available for applications up
to 800 A, with factory orderable options for voltage measure-
ment and positive temperature coefficient (PTC) protection.
Measurement Module
Safety Manual MN042004EN March 2017 www.eaton.com
Safety Considerations
RS-485
CH1 Port
CH2 Port
3

Advertisement

Table of Contents
loading