YASKAWA V1000 MMD Quick Start Manual page 39

Ip65 motor mounted drive, 400 v class, three-phase input: 1.5 to 5.5 kw

Advertisement

Par.
Name
Duty Mode and Carrier Frequency
Normal/
0: Heavy Duty (HD)
C6-01
Heavy Duty
1:Normal Duty (ND)
Selection
1:2.0 kHz
2:5.0 kHz
3:8.0 kHz
Carrier
4:10.0 kHz
C6-02
Frequency
5:12.5 kHz
Selection
6:15.0 kHz
7 to A: Swing PWM1 to 4
F: User defined
Frequency References
d1-01
Frequency
Set the multi-speed references 1 to
to
Reference
16.
d1-16
1 to 16
d1-17 Jog Speed
Jog speed
V/f Pattern
Motor Codes Description
3
SPRiPM 8 poles
E5-01
2
3000 rpm
<1>
3
1500 rpm
35 to
400 V, 1.5 kW to 18.5 kW
3F
Refer to Motor Codes for E5-01 on page 35
<1>
for a complete overview of available motor codes.
Digital Input Settings
H1-01
DI S1 to S6
Selects the function of terminals S1
to
Function
to S6.
H1-06
Selection
Major functions are listed at the end of the table.
Digital Output Settings
DO MA/MB
Set the function for the relay output
H2-01
Function
MA-MB-MC.
DO P1
Sets the function for the photocou-
H2-02
Function
pler output P1.
DO P2
Sets the function for the photocou-
H2-03
Function
pler output P2.
Major functions are listed at the end of the table.
YASKAWA Europe TOEP C710606 101A - V1000 MMD IP65 Motor Mounted Drive - Quick Start Guide
Description
6 Parameter Table
Par.
Name
Analog Input Setting
A1 Signal
0:0 to +10 V (neg. input is zeroed)
H3-01
Level Sel.
1:0 to +10 V (bipolar input)
A1
H3-02
Function
Assign a function to terminal A1.
Sel.
Sets the input value in % at 10 V
H3-03 A1 Gain
analog input.
Sets the input value in % at 0 V
H3-04 A1 Bias
analog input.
0:0 to +10 V (neg. input is zeroed)
A2 Signal
1:0 to +10 V (bipolar input)
H3-09
Level
2:4 to 20 mA (9 bit input)
Selection
3:0 to 20 mA
A2
H3-10
Function
Assign a function to terminal A2.
Sel.
Sets the input value in % at
H3-11 A2 Gain
10 V/20 mA analog input.
Sets the input value in % at
H3-12 A2 Bias
0 V/0 mA/4 mA analog input.
Analog Input Setting
AM
Enter value equal to U1-
H4-01
Monitor
monitor values. Example: Enter
Selection
"103" for U1-03.
Sets terminal AM output voltage
H4-02 AM Gain
equal to 100% monitor value.
Sets terminal AM output voltage
H4-03 AM Bias
equal to 0% monitor value.
Pulse Input Setting (Free. ref. input)
RP Input
Sets the number of pulses (in Hz)
H6-02
Scaling
that is equal to 100% input value.
Pulse Train
Sets the input value in % at pulse
H6-03
Input Gain
input with H6-02 frequency.
Pulse Train
Sets the input value in % at 0 Hz
H6-04
Input Bias
pulse input frequency.
Pulse Output Setting
Enter value equal to U-
MP Monitor
H6-06
monitor values. Example: Enter
Sel.
"102" for U1-02.
MP Monitor
Sets the number of output pulses
H6-07
Scaling
when the monitor is 100% (in Hz).
Description
EN 39