5 Start Up
 Reference and Run Source
The drive has a LOCAL and a REMOTE mode.
Status
LOCAL
REMOTE
If the drive is operated in the REMOTE mode, make sure that the correct sources for the fre-
quency reference and run command are set in parameters b1-01/02 and that the drive is in
the REMOTE mode.
The LED in the LO/RE key indicates where the Run command is input from.
LO/RE LED
ON
OFF
 I/O Setup
Multi-Function Digital Inputs (H1-)
The function of each digital input can be assigned in the H1- parameters. The default set-
ting functions can be seen in the connection diagram on
Multi-Function Digital Outputs (H2-)
The function of each digital output can be assigned in the H2- parameters. The default
setting functions can be seen in the connection diagram on
these parameters consist of 3 digits, where the middle and right digit set the function and the
left digit sets the output characteristics (0: Output as selected; 1: Inverse output).
Multi-Function Analog Inputs (H3-)
The function of each analog input can be assigned in the H3- parameters. The default
setting of both inputs is "Frequency bias". Input A1 is set for 0 to 10V input and A2 is set for
4-20 mA input. The addition of both input values builds the frequency reference.
NOTICE! If the input signal level of input A2 is switched between voltage and current, make
sure that DIP switch S1 is in the correct position and parameter H3-09 is set up
correctly.
Monitor Output (H4-)
Use the H4- parameters to set up the output value of the analog monitor output and to
adjust the output voltage levels. The default monitor value setting is "Output frequency".
EN 36
YASKAWA Europe TOEP C710606 101A - V1000 MMD IP65 Motor Mounted Drive - Quick Start Guide
The Run/ Stop command and the frequency reference are entered at the operator keypad.
The Run command source entered in parameter b1-02 and the frequency reference
source entered in parameter b1-01 are used.
Run command is issued from operator.
Run command is issued from a different source than the operator.
Description
Description
page
24.
page
24. The setting value of