 Frequency Reference and Acceleration/ Deceleration Times
Frequency Reference Setup(b1-01)
Set parameter b1-01 according to the frequency reference used.
b1-01
Reference source
0
Operator keypad
1
Analog input
2
Serial Comm.
3
Option Board
4
Pulse input
Acceleration/ Deceleration Times and S-Curves
There are four sets of acceleration and deceleration times which can be set in the C1-
parameters. The default activated accel/decel times are C1-01/02. Adjust these times to the
appropriate values required by the application. If necessary S-curves can be activated in the
C2- parameters for softer accel/decel start and end.
 Test Run
Perform the following steps to start up the machine after all parameter settings have been
done.
1. Run the motor without load and check if all input, outputs and the sequence work as
desired.
2. Connect the load to the motor.
3. Run the motor with load and make sure that there is no vibrations, hunting or motor
stalling occurs.
After taking the steps listed above, the drive should be ready to run the application and per-
form the basic functions. For special setups like PID control etc. refer to the Technical Man-
ual.
YASKAWA Europe TOEP C710606 101A - V1000 MMD IP65 Motor Mounted Drive - Quick Start Guide
Frequency reference input
Set the frequency references in the d1- parameters and used digital inputs to
switch over between different reference values.
Apply the frequency reference signal to terminal A1 or A2.
Serial Communications using the RS422/485 port
Communications option card
Set the frequency reference at terminal RP using a pulse train signal.
5 Start Up
EN 37