Download Print this page

YASKAWA V1000 MMD Quick Start Manual page 42

Ip65 motor mounted drive, 400 v class, three-phase input: 1.5 to 5.5 kw

Advertisement

6 Parameter Table
Monitor
Fault History
U3-01
Lists the most recent fault that occurred
to
through the fourth most recent fault.
U3-04
U3-05
Accumulated operation time at the most recent
to
fault through the fourth most recent fault.
U3-08
U3-09 to
Lists the fifth most recent fault that occurred
U3-14
through the tenth most recent fault.
Accumulated operation time at fifth most
U3-15 to
recent fault through the tenth most recent
U3-20
fault.
* The following faults are not recorded in the error log:
CPF00, 01, 02, 03, UV1, and UV2.
Par.
Name
Control Monitor
Motor Sec-
Displays the value of the motor
U6-01
ondary Cur-
secondary current (Iq).
rent (Iq)
Motor Exci-
Displays the value calculated for
U6-02
tation Cur-
the motor excitation current (Id).
rent (Id)
Output volt-
Output voltage reference (Vq).
U6-05
age refer-
(q-axis)
ence (Vq)
Output
Voltage
Output voltage reference (Vd).
U6-06
Reference
(d-axis)
(Vd)
Frequency
Reference
Displays the bias value used to
U6-20
Bias (Up/
adjust the frequency reference.
Down 2)
Offset Fre-
Displays the frequency added to
U6-21
quency
the frequency reference.
EN 42
YASKAWA EuropeTOEP C710606 101A - V1000 MMD IP65 Motor Mounted Drive - Quick Start Guide
Description
Description
DI/DO
Description
Sel.
Digital Input Function Selection
3
Multi-step speed reference 1
4
Multi-step speed reference 2
5
Multi-step speed reference 3
Jog frequency command (higher priority than
6
multi-step speed reference)
7
Accel/decel time selection 1
F
Not used (Set when a terminal is not used)
14
Fault reset (Reset when turned ON)
External fault; Input mode: N.O. contact /
20 to 2F
N.C. contact, Detection mode: Normal/during
operation
Digital Output Function Selection
During Run (ON: run command is ON or volt-
0
age is being output)
1
Zero Speed
2
Speed Agree
6
Drive Ready
E
Fault
F
Not used
10
Minor fault (Alarm) (ON: Alarm displayed)

Advertisement

loading

This manual is also suitable for:

Sp-v1m