Ip65 motor mounted drive, 400 v class, three-phase input: 1.5 to 5.5 kw

Advertisement

 Wiring Specification
Main Circuit
Use the wire gauges listed up in the table below when wiring the main circuit. Make sure not
to exceed the given tightening torque values.
Model
Recom. Motor cable
V1MC-A
40004
40005
40007
40009
40011
Input Fuse Selection
Branch circuit protection shall be provided by any of the following:
• Non-time delay Class J, T, or CC fuses sized at 300% of the drive input rating
Exceptional models are A6T20 with 4A0005, and A6T25 with 4A0007.
Note:
• Time delay Class J, T, or CC fuses sized at 175% of the drive input rating
• Time-delay Class RK5 fuses sized at 225% of the drive input rating
Non-Time Delay
Model
Class-T Fuse Type
V1MC-A
(Manufacturer: Ferraz)
600 Vac, 200 kAIR
40004
40005
40007
40009
40011
YASKAWA Europe TOEP C710606 101A - V1000 MMD IP65 Motor Mounted Drive - Quick Start Guide
Filter Terminal Sizes L1, L2, L3
Applicable Gauge
(mm²)
2.5
Fuse Ampere
Rating (A)
A6T15
A6T20
A6T25
A6T25
A6T30
3 Electrical Installation
Screw Size
(mm²)
2.5 to 6
M5
Fuse Type
(Manufacturer:
Bussmann)
500 Vac, 200 kAIR
15
FWH-50B
20
FWH-70B
25
FWH-70B
25
FWH-90B
30
FWH-90B
Tightening Torque
(N×m (lb.in.))
2.0 to 2.5 (17.7 to 22.1)
Fuse Ampere
Rating (A)
50
70
70
90
90
EN 25