WAGO-I/O-SYSTEM 750 XTR
750-468/040-000 4AI 0-10V DC S.E. /XTR
Pos : 28 /Serie 750 ( WAGO-I/O-SYST EM)/Ger ätebesc hrei bung (alte Str uktur)/Ansc hlüsse/Leistungskontakte/F eldvers orgung - Ü berschrift 3 @ 6\mod_1256294692864_21.doc x @ 43664 @ 3 @ 1
3.2.2

Power Jumper Contacts/Field Supply

Pos : 29 /Serie 750 ( WAGO-I/O-SYST EM)/Ger ätebesc hrei bung (alte Str uktur)/Ansc hlüsse/Leistungskontakte nicht vorhanden @ 8\mod_1281073936319_21.doc x @ 62530 @ @ 1
The I/O module 750-468/040-000 has no power jumper contacts.
Pos : 30 /Serie 750 ( WAGO-I/O-SYST EM)/Ger ätebesc hrei bung (alte Str uktur)/Ansc hlüsse/CAGE CLAMP- Ans chl üss e - Ü bersc hrift 3 @ 6\mod_1256296337770_21.doc x @ 43674 @ 3 @ 1
3.2.3
CAGE CLAMP
Pos : 31 /Serie 750 ( WAGO-I/O-SYST EM)/Ger ätebesc hrei bung (alte Str uktur)/Ansc hlüsse/AI/Ansc hlüsse 750-0468 @ 16\mod_1377245737103_21.doc x @ 129476 @ @ 1
Figure 3: CAGE CLAMP

Table 4: Legend for Figure "CAGE CLAMP

Channel Designation Connector Function
1
2
3
4
-
-
-
-
Pos : 32 /Serie 750 ( WAGO-I/O-SYST EM)/Wic htige Erläuterungen (al te Str uktur)/Sic herheits- und sonstige Hinweis e/Hinweis/Hi nwei s: Ges chir mte Signall eitungen ver wenden! @ 7\mod_1265723251019_21.doc x @ 50140 @ @ 1
Use shielded signal lines!
Only use shielded signal lines for analog signals and I/O modules which are
equipped with shield clamps. Only then can you ensure that the accuracy and
interference immunity specified for the respective I/O module can be achieved
even in the presence of interference acting on the signal cable.
Pos : 33 /Serie 750 ( WAGO-I/O-SYST EM)/Ans chli eßen/Ver weis auf Kapitel Schir mung i m Systemhandbuc h XTR @ 19\mod_1399554643119_21.doc x @ 153199 @ @ 1
For further information about shielding, see system manual WAGO-I/O-SYSTEM
750 XTR, section "Connect Devices" > ... > "Shielding."
Pos : 34 /D okumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
®
Connectors
®
Connectors
AI 1
1
AI 2
5
AI 3
2
AI 4
6
3
Common
(ground)
7
4
Shield
(screen)
8
®
Connectors"
Analog input 1: Signal
Analog input 2: Signal
Analog input 3: Signal
Analog input 4: Signal
Ground potential of the analog input circuit
Ground potential of the analog input circuit
Shield termination
Shield termination