PSG G1N 4R9 Installation And Operating Instructions Manual

Wood and combined wood-electric furnaces

Advertisement

Installation and Operating
Instructions for Wood and
Combined Wood-electric Furnaces
THIS MANUAL CONCERNS THE FOLLOWING FURNACES
WOOD
PSG-2000
PSG-3000
PSG-4000
PSG-4500
PSG-5000
All the instructions must be read carefully
before installing and operating furnace.
CONGRATULATIONS!
You have just purchased one of the best wood or combined
wood-electric furnace on the market.
We are convinced that your furnace will provide you
with many years of comfort, safely.
Keep these instructions!
Stove Builder International Inc.
1700, Léon-Harmel
COMBINED ELECTRIC
15 KW, 18 KW, 20 KW
15 KW, 18 KW, 20 KW, 25 KW
18 KW, 20 KW, 25 KW, 30 KW
18 KW, 20 KW, 25 KW, 30 KW
40 KW, 50 KW, 60 KW
Québec(Québec)
G1N 4R9

Advertisement

Table of Contents
loading

Summary of Contents for PSG G1N 4R9

  • Page 1 COMBINED ELECTRIC 15 KW, 18 KW, 20 KW 15 KW, 18 KW, 20 KW, 25 KW 18 KW, 20 KW, 25 KW, 30 KW 18 KW, 20 KW, 25 KW, 30 KW 40 KW, 50 KW, 60 KW G1N 4R9...
  • Page 2: Table Of Contents

    INTRODUCTION ... 4 1. CHIMNEY AND DRAFT... 4 2. SAFETY RULES... 4 GENERAL REQUIREMENTS ... 4 ODOUR FROM THE PAINT ... 5 ASH DISPOSAL ... 5 CREOSOTE BUILD-UP AND REMOVAL SMOKE DETECTOR ... 6 ASH DRAWER ... 6 ASH GRATE ...
  • Page 3 10. SELECTION CRITERIA (COMBINED WOOD/ELECTRIC FURNACE) ... 28 11. TROUBLESHOOTING... 29 12. DUCTS AND REGISTER MEASUREMENTS ... 30 LIMITED LIFETIME WARRANTY ... 31...
  • Page 4: Introduction

    INTRODUCTION To get maximum performance from your PSG furnace, keep in mind the following: • Comply with local codes (if in doubt, contact your local heating specialist). • Refer to the furnace’s certification label and your instruction manual for minimum installation clearances. •...
  • Page 5: Odour From The Paint

    -THE ASH DRAWER GET VERY HOT. -DO NOT MANIPULATE WITH BARE HANDS. ODOUR FROM THE PAINT It is normal that a smoke odor emanate from the unit when you first light it. It is recommended to burn it at high rate and ventilate the building until the odour resorbs.
  • Page 6: Smoke Detector

    SMOKE DETECTOR We highly recommend the use of a smoke detector. It must be installed at least 15 feet (4,57 m) from the appliance in order to prevent undue triggering of the detector when reloading. ASH DRAWER Your appliance is equipped with an ash drawer to collect ashes produced by the combustion of wood. This drawer must not be left open during combustion as this will cause over firing and serious damage to the furnace.
  • Page 7: Clearances To Combustible Materials

    CLEARANCES TO COMBUSTIBLE MATERIALS N.B. This appliance must be installed in accordance with the instructions on the unit’s certification. MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS FOR PSG FURNACES N.B. THE AIR RETURN CONDUITS SHOULD BE AT LEAST EQUAL TO THE COLD AIR PLENUM DIMENSIONS.
  • Page 8: Damper

    For a proper installation, follow the advices below: 1. All the joints of the evacuation pipe must be secured, using three screws. Make sure that each screw goes through the inner walls of both connectors (male and female). See pictures below showing a male-female coupling. PROPER INSTALLATION 2.
  • Page 9: Electrical Connection

    NOTE: It is recommended to install an outside air inlet of minimum 4” diameter in the room where the heating appliance is installed (see drawing below). To do so, it is preferable to choose a wall which is not exposed to extreme winds, according to the conditions surrounding your house.
  • Page 10: Electric Element

    The switch located on the fan limit control activates the blower at high speed, in either automatic or manual (continuous operation) modes. The switch located on the electric unit controls low speed operation, in either ON (continuous operation) or OFF modes (PSG 3000 or PSG 4000 models only).
  • Page 11: Thermostat

    OUTSIDE VIEW OF THE ELECTRIC ELEMENT THERMOSTAT The thermostat must be installed on an inside wall in a location where it is not likely to be affected by the draft coming from an air outlet. It must be installed at a minimum of 55 inches above the floor. N.B.
  • Page 12: Operating Instructions

    4. OPERATING INSTRUCTIONS Control system On the wood furnaces only, the thermostat controls the air inlet damper. When the thermostat calls for heat, the damper opens and the fire burns up. When the furnace gets hot enough, the combined limit control activates the blower motor at the speed selected for wood heating.
  • Page 13: Heating

    HEATING 1. When loading the furnace, lower the kindled pieces of wood and place them at the center of the combustion chamber before adding new logs. 2. Do not overload. Air must circulate freely in the upper part of the furnace in order to obtain an efficient operation of the appliance.
  • Page 14: Chimney Fires

    Whenever a high rate of smoke is noticed in the room, you must: 1. Open doors and windows. 2. Make sure the furnace door is closed as well as the damper (if necessary, lower the thermostat starting point or undo the chain of the damper and close manually the barometric draft control). 3.
  • Page 15: Maintenance

    5. MAINTENANCE MAINTENANCE OF THE EXCHANGERS The evacuation pipe and the exchangers should be inspected regularly during the burning season. Using the scraper, clean the three exchanger pipes. INSTRUCTIONS Wait until fire is completely out before cleaning. Remove the smoke pipe connector from the furnace. Inspect the furnace’s heat exchangers (rectangular tubes) through the smoke outlet for creosote accumulation.
  • Page 16: Filters

    FILTERS The furnace must not be operated without the filters. In order to operate a slow combustion heating system efficiently and safely, you have to ensure a regular maintenance. This means that the chimney, the joints and the flue must be in good condition. The air filters must be replaced regularly. Use the same size and same type as the original filters.
  • Page 17: Electric Diagrams For Units Built From 2005

    7. ELECTRIC DIAGRAMS FOR UNITS BUILT FROM 2005 FAN LIMIT HONEYWELL L6064(MOTOR (G-10) 4 SPEED AND (G-12) 2 SPEED) THERMOSTAT SERVO-MOTOR 24 V.A.C. 24 V.A.C. REVISION JUNE 17TH 2005 WOOD-ONLY FURNACES HONEYWELL L6064 LIMIT LINE LOAD HIGH LINE JUNCTION BOX BLUE BLACK 120 V.A.C.
  • Page 18: Wood/Electric Furnaces

    WOOD/ELECTRIC FURNACES FAN LIMIT HONEYWELL L6064(MOTOR (G-10) 4 SPEED AND (G-12) 2 SPEED) ELEMENTS HONEYWELL POWER BLOCK L6064 240V LIMIT ON 150°F OFF 110°F LIMIT 250°F LINE LOAD HIGH LINE 20 A TRANSFO POWER BLACK 120V COMMAND BLOCK BLOCK POWER BLACK COMMAND BLOCK...
  • Page 19: Psg5000 Wood-Only Furnaces

    FAN LIMIT HONEYWELL L6064(MOTOR (G-12) 2 SPEED) THERMOSTAT SERVO-MOTOR 24 V.A.C. 24 V.A.C. REVISION JUNE 21ST 2005 PSG5000 WOOD-ONLY FURNACES HONEYWELL L6064 ON 150°F OFF 110°F LIMIT LIMIT 250°F LINE LOAD LOW HIGH LINE JUNCTION BOX 120 V.A.C. TRANSFORMER 24 V.A.C. HONEYWELL L6064 LIMIT...
  • Page 20: Psg5000 Wood/Electric Furnaces

    FAN LIMIT HONEYWELL L6064(MOTOR (G-12) 2 SPEED) HONEYWELL L6064 ON 150°F OFF 110°F ELEMENTS LIMIT LIMIT 250°F COIL 25KW OR 30 KW ONLY POWER BLOCK LINE LOAD TRANSFO HIGH LINE 240V 240V RELAY 40VA POWER 20 A BLOCK L-170 RESET 5 KW ELEM.
  • Page 21: Electric Diagrams For Units Built Before 2005

    8. ELECTRIC DIAGRAMS FOR UNITS BUILT BEFORE 2005 THERMOSTAT SERVO-MOTOR 24 V.A.C. 24 V.A.C. 15 MARS 1990 WOOD ONLY FURNACES PSG 4000 & 4500 BELT-DRIVE G12 MOTOR WHITE RODGERS JUNCTION BOX 120 V.A.C. TRANSFORMER 24 V.A.C. HONEYWELL L4064 ON 150°F OFF 110°F...
  • Page 22: Wood Only Furnaces Psg 5000

    IMPORTANT: A BREAKER IS MANDATORY FOR 240 VOLT VERIFY CONNECTIONS OF THE MOTOR 3/4 H.P. IF CONNECTED ONTO THE RIGHT CIRCUIT(120/240) WOOD ONLY FURNACES PSG 5000 BELT-DRIVE G12 MOTOR WHITE RODGERS ON 150°F OFF 110°F LIMIT 250°F BLACK JUNCTION BOX 120 V.A.C.
  • Page 23: Wood/Electric Furnaces Psg 4000 & 4500

    WOOD/ELECTRIC FURNACES PSG 4000 & 4500 WHITE RODGERS HONEYWELL L4064 ON 150°F OFF 110°F WHITE LIMIT 250°F ELEMENTS LOW SPEED SWITCH BLACK POWER BLOCK 110 VOLT MOTOR 3/4 H.P. FOR 240 V 240V TRANSFO BLACK 120V COMMAND POWER BLOCK BLOCK...
  • Page 24: Wood/Electric Furnaces Psg 5000 40Kw @ 60Kw

    WOOD/ELECTRIC FURNACES PSG 5000 40KW @ 60KW HONEYWELL WHITE RODGERS L4064 ON 150°F BLACK FROM TRANSFO OFF 110°F COIL LIMIT 250°F BLACK ELEMENTS TRANSFO 240V POWER BLOCK RELAY 40VA 110 VOLT LINE 3/4 H.P. MOTOR 240 V POWER 240V BLOCK 5 KW ELEM.
  • Page 25: Wood Only Furnaces Psg 2000-3000-4000

    WOOD ONLY FURNACES PSG 2000-3000-4000 THERMOSTAT SERVO-MOTOR 24 V.A.C. 24 V.A.C. REVISION MAY 20TH 1994 DIRECT-DRIVE G10 MOTOR WHITE RODGERS RELAY JUNCTION BOX BLACK 120 V.A.C. TRANSFORMER 24 V.A.C. HONEYWELL L4064 BLACK FROM ON 150°F TRANSFO OFF 110°F LIMIT 250°F 120 V.A.C.
  • Page 26: Wood/Electric Furnaces Psg 2000-3000-4000

    WOOD/ELECTRIC FURNACES PSG 2000-3000-4000 HONEYWELL WHITE RODGERS L4064 ON 150°F BLACK TO TRANSFOMER OFF 110°F LIMIT 250°F BLACK ELEMENTS POWER BLOCK 240V 20 A TRANSFO BLACK 120V COMMAND POWER BLOCK BLOCK POWER BLACK COMMAND BLOCK RELAY BLOCK 20VA BLOWER 4 SPEED...
  • Page 27: Technical Specifications

    9. TECHNICAL SPECIFICATIONS 2000 3000 4000 4500 5000 45 ¼" 47" 50" 23 ½" 25 ½" 29 ½" 33 ½" 45 ½" 47 ¼" 48" 15 ⅞" 15 ⅞" 19" 26 ⅜" 28" 28" 22 ½" 24 ½" 28 ½" 32 ½" 51 ⅛" 40 ½"...
  • Page 28: Selection Criteria (Combined Wood/Electric Furnace)

    10. SELECTION CRITERIA (COMBINED WOOD/ELECTRIC FURNACE) RESIDENTIAL AREA House including: basement, first floor and second floor (half) Floor area * 1100 square feet or less 1100 to 1450 square feet 1400 to 2000 square feet 2000 to 3000 square feet COMMERCIAL AREA Building including: Walls 14 to 16 feet high...
  • Page 29: Troubleshooting

    11. TROUBLESHOOTING PROBLEM 1. Sudden drop in heating performance follows adequate heating from first loadings. 2. Insufficient heat from first loadings, low draft 3. Poor heating in the rooms while hot air plenum and furnace are hot. 4. Furnace burns too much wood. 5.
  • Page 30: Ducts And Register Measurements

    12. DUCTS AND REGISTER MEASUREMENTS SIMPLIFIED METHOD DISTRIBUTION SYSTEM Ducts size (heat) 4 inch outlet reduce by 1” 5 inch outlet reduce by 2” Always by 8” thick 6 inch outlet reduce by 3” N.B.: The main duct must be reduced every 2 outlets.
  • Page 31: Limited Lifetime Warranty

    1700, rue Léon-Harmel, Québec (Québec) G1N 4R9 e-mail : tech@sbi-international.com web site : www.psg-distribution.com The PSG warranty extends only to the original consumer purchaser and is not transferable. This warranty covers brand new products only, which have not been altered, modified nor repaired since shipment from factory. Proof of purchase (dated bill of sale), model name and serial number must be supplied when making any warranty claim to your PSG dealer This warranty applies to normal use only.

This manual is also suitable for:

Psg-2000Psg-3000Psg-4000Psg-4500Psg-5000