6.3.1
Infrared & KYZ Pulse Constants for Accuracy Testing
Note
6–6
WATT-HOUR ACCURACY TESTING (VERIFICATION)CHAPTER 6: USING THE METER
Table 6–2: Infrared & KYZ Pulse Constants for Accuracy Testing
Voltage Level
Below 150 V
Above 150 V
•
Minimum pulse width is 40 ms.
•
Refer to section 2.2 for Wh Pulse specifications.
Class 10 Models
0.2505759630
1.0023038521
EPM6000 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE
Class 2 Models
0.0501151926
0.2004607704