EPM6000 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE
CHAPTER 5: COMMUNICATION INSTALLATIONEPM6000 COMMUNICATION AND PROGRAMMING OVERVIEW
LIMITS (VSwitch 4 Only)
For up to 8 Limits, Set:
Address: Modbus Address (1 based)
Label: Your Designation
High Set Point: % of Full Scale
Example: 100% of 120VFS = 120V
90% of 120V FS = 108V
Return Hysteresis: Point to go back in Limit
Example: High Set Point = 110%
(Out of Limit at 132V)
Return Hysteresis = 105%
(Stay Out until 126V)
Low Set Point:: % of Full Scale
Return Hysteresis: Point to go back in Limit
Settings appear in the Table at the bottom of the screen
If Return Hysteresis is > High Set Point, the Limit is Disabled.
Click Update to send a new Profile.