Regency City Series Owners & Installation Manual page 43

Zero clearance direct flue gas fireplace
Hide thumbs Also See for City Series:
Table of Contents

Advertisement

Horizontal Terminations
Rigid Pipe 102mm x 175mm
The diagrams below show examples of horizontal termination arrangements using one, two, or three 90
1. A maximum of three 90
o
elbows are permitted.
2. Minimum distance between elbows is 305mm.
Maintain clearances to combustibles as listed in the "Clearances" section.
Horizontal flue must be supported every 0.9m.
Firestops are required at each floor level and whenever passing through a wall.
Must use optional rigid pipe adaptor (Part# 510-994) when using rigid pipe flue systems.
A flue guard should be used whenever the termination is lower than the specified minimum or as per local codes.
Flex system can only be used up to 3m - otherwise rigid flueing must be used.
Horizontal Venting with Two (2) 90
One 90
o
elbow = Two 45
Option
V
H + H1
Min.
Max.
A)
0.3m
0.6m
B)
0.6m
1.2m
C)
0.9m
1.5m
D)
1.2m
1.8m
E)
1.5m
2.1m
F)
1.8m
2.4m
Restrictor Set 0 - Factory Setting
H1
o
Elbows
o
elbows.
W i t h t h e s e o p t i o n s ,
maximum total pipe length
is 9.1m with minimum of
1.8m feet total vertical
and maximum 2.4m total
horizontal.
Please note minimum
o
0.3m between 90
elbows
is required.
V
o
elbows (two 45
Horizontal Venting with Three (3) 90
One 90
o
elbow = Two 45
Option
V
H
Min.
Max.
A)
0.3m
0.3m
B)
0.3m
0.6m
C)
0.6m
0.6m
D)
0.9m
0.6m
E)
1.2m
0.9m
F)
1.5m
1.2m
G)
1.8m
1.5m
H)
2.1m
1.8m
Restrictor Set 0 - Factory Setting
installation
o
elbows equal one 90
o
elbow)
o
Elbows
o
elbows.
V + V1
H + H1
With these options,
Min.
Max.
max. total pipe
length is 9.1m with
0.6m
0.6m
min. of 3.6m total
0.9m
0.9m
vertical and max.
2.7m total horizon-
1.5m
1.2m
tal.
2.1m
1.5m
Please note min.
2.7m
1.8m
0.3m between 90
3m
2.1m
elbows is required.
3.3m
2.4m
3.6m
2.7m
City Series ACC40E |
o
43

Advertisement