Technical Data; The Beckhoff Bus Terminal System - Beckhoff BK9053 Documentation

Bus coupler for profinet
Table of Contents

Advertisement

data in order to manage and store them centrally. This means that it is not necessary to carry out the setting
procedure again if a Bus Terminal is exchanged. The controller carries out the desired setting automatically
after switching on.
2.3

Technical data

System
System data
Number of I/O modules
Number of I/O points
Transmission medium
Distance between modules
Data transfer rate
Topology
Cascading
Bus Coupler
Technical data
Number of Bus Terminals
Digital peripheral signals
Analog peripheral signals
Protocols
Configuration possibility
Maximum number of bytes
Bus connection
Power supply
Current consumption
Starting current
K-Bus power supply up to
Power contact voltage
Power contact current load
Dielectric strength
Recommended fuse
Weight
Mounting [} 15]
Permissible ambient temperature range dur-
ing operation
Permissible ambient temperature range dur-
ing storage
Permissible relative humidity
Vibration/shock resistance
EMC immunity/emission
Installation position
Protection class
Approvals
2.4

The Beckhoff Bus Terminal system

Up to 256 Bus Terminals, with 1 to 16 I/O channels per signal form
The Bus Terminal system is the universal interface between a fieldbus system and the sensor / actuator
level. A unit consists of a Bus Coupler as the head station, and up to 64 electronic series terminals, the last
one being an end terminal. Up to 255 Bus Terminals can be connected via the K-bus extension. For each
BK9053, BK9103
BK9053
only limited by the IP address space
depending on controller
Twisted pair copper cable, 4 x 2, shielded; category 5 (100 Mbaud)
100 m (between switch and Bus Coupler)
10/100 Mbaud
line or star wiring
up to 20 Bus Couplers (max. line length 2 km)
BK9053
64 (255 with K-bus extension)
512 inputs/outputs
256 inputs/outputs
PROFINET RT (class B)
TCP-ADS for access via Ethernet with KS2000 configuration software
Via the KS2000 configuration software or the controller
512 bytes of input data and 512 bytes of output data
1 x RJ45
24 V
(-15%/+20%)
DC
70 mA + (total K bus current)/4, max. 500 mA
approx. 2.5 x continuous current
1750 mA
maximal 24 V
DC
maximal 10 A
500 V (power contact/supply voltage/Ethernet/fieldbus)
≤ 10 A
approx. 100 g
on 35 mm mounting rail conforms to EN 60715
0 °C ... +55 °C
-25 °C ... +85 °C
95 %, no condensation
conforms to EN 60068-2-6 / EN 60068-2-27
conforms to EN 61000-6-2 / EN 61000-6-4
variable
IP20
CE, UL, ATEX [} 21]
Version: 2.3.0
Product overview
BK9103
BK9103
512 inputs/outputs
256 inputs/outputs
2 x RJ45
approx. 170 g
-25 °C ... +60 °C
-40 °C ... +85 °C
CE, UL, ATEX [} 22], GL