Configuration

5.1

GSDML configuration files

The latest PROFINET master configuration file for the Bus Couplers BK9053 and BK9103 can be found on
the Beckhoff website under Downloads:
http://www.beckhoff.de/german/download/bkconfg.htm
5.2

Mapping the Bus Terminals

The KLxxxx or KSxxxx Bus Terminals are mapped to the Bus Coupler in the order in which the hardware is
connected. No distinction is made between KLxxxx and KSxxxx Bus Terminals. Bus Terminals without
process image cannot be configured (e.g. KL9100, KL9020, KL9050, KL9010).
For digital Bus Terminals at least one byte is reserved in all cases.
Example: KL1xx2 2 digital inputs, 8 bit, with the first two bits 0-1 reserved for the terminal. Bits 2-7 are not
used.
Complex Bus Terminals are represented with an input and output process image.
Sample: KL3001 1 analog input 1 Byte Control or Status Information, one empty byte, 2 Byte Data.
5.3

Configuration example with Step 7

Install the GSDML file (Step 7 from version 5.4 + SP1)
To this end open the hardware manager. Install the GSDML file.
Fig. 17: Step 7 - installing the GSDML file
Add a BK9103 as a node in your Manager, then add the terminals according to your configuration.