Parameterization and commissioning
4.4

IP address

Usually the IP address is specified by the PROFINET controller and therefore does not need to be set in the
bus coupler. The bus couplers are addressed via the PROFINET-Name which can be set using various
procedures (see DIP switch settings [} 25]).
In exceptional cases it makes sense to give the bus coupler an IP address in advance (without connecting
PROFINET), e.g. to access the couplers via KS2000 Software and Ethernet.
4.4.1

IP address and PROFINET name

The IP address can be set using three different procedures, and these will be described in more detail below.
Procedure
Explanation
KS2000
Addressing using the KS2000
configuration software and DIP switches
[} 28]
BootP
Addressing via BootP server [} 30]
DHCP
Addressing via DHCP server [} 31]
4.4.2

Configuration with KS2000

The KS2000 configuration software (from version 3.2.8) can be used to set the TCP/IP address in a dialog
box, or it can be written directly into the registers. DIP switches 9 and 10 (for BK9050 DIP switches 1 and 2
in blue) should both be OFF (0) before switching on.
Table 100
Register
0
1
Default
Byte
1
2
3
4
Sample
Fig. 14: DIP switch
Switch no.
1
Valence
1
In this example ON
Value
1
28
High-Byte
IP-Byte 2
Not used
Default value (hex)
0xAC
0x10
0x11
(DIP switch)
2
3
4
5
2
4
8
16
OFF
OFF ON
OFF
0
0
8
0
Version: 2.3.0
Necessary components
KS2000 configuration software and KS2000 cable
BootP-Server
DHCP-Server
Low-Byte
IP-Byte 1
IP-Byte 3
Default value (dec)
172
dec
16
dec
17
dec
(0 to 255
dec
6
7
8
9
32
64
128
-
OFF
ON
ON
OFF
0
64
128
-
)
10
-
OFF
-
Total=201