All the components are supplied in particular hardware and software configurations appropriate for the application. Modifications to hardware or software configurations other than those described in the documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH & Co. KG. Personnel qualification This description is only intended for trained specialists in control, automation and drive engineering who are familiar with the applicable national standards.
Documentation Issue Status Version Comment 1.0.0 • First published Firmware and hardware versions Documentation KL2819 Version Firmware Hardware 1.0.0 The firmware and hardware versions (delivery state) can be taken from the serial number printed on the side of the terminal.
HD Bus Terminal, 16-channel digital output 24 V DC, 0.5 A, with diagnostics The KL2819 Bus Terminal has 16 digital output channels for the switching of 24 V loads up to 0.5 A. The integrated diagnostics can be evaluated by the controller and indicated by the LEDs. Overtemperature and the lack of a voltage supply to the terminal are supplied as diagnostic information.
KL2819 - Introduction and technical data Technical data Technical data KL2819 Connection technology 1-wire Number of Outputs Rated load voltage 24 V DC (-15 %/+20 %) Current consumpt. K-bus typ. 30 mA Load type ohmic, inductive, lamp load Max. output current 0.5 A (short-circuit-proof) per channel...
KL2819 - Introduction and technical data Fig. 2: Overload current limitation Fig. 3: Schematic illustration of the thermal switch-off in case of overload In case of a long-term overload and/or short-circuit, the output is protected by the thermal switch-off of the channel.
Note flict with the fixing bolts of the mounting rail. To mount the mounting rails with a height of 7.5 mm under the terminals and couplers, you should use flat mounting connections (e.g. countersunk screws or blind rivets). Version: 1.0.0 KL2819...
PE power contact The power contact labeled PE can be used as a protective earth. For safety reasons this contact mates first when plugging together, and can ground short-circuit currents of up to 125 A. KL2819 Version: 1.0.0...
• The terminals of KSxxxx and ESxxxx series feature a pluggable connection level and enable steady wiring while replacing. • The High Density Terminals (HD Terminals) include electronics and connection level in a single enclosure and have advanced packaging density. Version: 1.0.0 KL2819...
12 mm Bus Terminals. Massive conductors and conductors with a wire end sleeve can be inserted directly into the spring loaded terminal point without tools. KL2819 Version: 1.0.0...
3. The terminal closes automatically when the pressure is released, holding the wire securely and per- manently. Terminal housing ELxxxx, KLxxxx ESxxxx, KSxxxx Wire size width 0.08 ... 2,5 mm 0.08 ... 2.5 mm Wire stripping length 8 ... 9 mm 9 ... 10 mm Version: 1.0.0 KL2819...
EL/KL terminals to face forward (see Fig. “Recommended distances for standard installation position”). The terminals are ventilated from below, which enables optimum cooling of the electronics through convection. "From below" is relative to the acceleration of gravity. KL2819 Version: 1.0.0...
Other installation positions All other installation positions are characterized by different spatial arrangement of the mounting rail - see Fig “Other installation positions”. The minimum distances to ambient specified above also apply to these installation positions. Version: 1.0.0 KL2819...
Fig. 13: Other installation positions ATEX - Special conditions Observe the special conditions for the intended use of Beckhoff fieldbus components in potentially explosive areas (directive 94/9/EU)! • The certified components are to be installed in a suitable housing that guarantees a...
Mounting and wiring Marking The Beckhoff fieldbus components certified for potentially explosive areas bear one of the following markings: II 3 G Ex nA II T4 KEMA 10ATEX0075 X Ta: 0 - 55°C II 3 G Ex nA nC IIC T4 KEMA 10ATEX0075 X Ta: 0 - 55°C...
Fieldbus Box modules with the aid of which settings can be modified easily. Alternatively, you have full access to all internal registers of the bus couplers and intelligent terminals. Refer to the register description for the meanings of the registers. KL2819 Version: 1.0.0...
All possibilities in the online mode can be used in parallel with the actual fieldbus mode of the terminal station. The fieldbus protocol always has the higher priority in this case. Register You can access the registers of the KL2819 directly under Register.– The meaning of the register is explained in the register overview. Version: 1.0.0...
Read access Write access CB.5 Reg. no. Register number: Enter here the number of the register that you wish CB.0 - to read with input data word DataIN, or - to write with output data word DataOUT. Version: 1.0.0 KL2819...
Page 25
The status byte (SB) is located in the input image, and is transmitted from terminal to the controller. Name Description SB.7 RegAccess 1 Acknowledgement for register access SB.6 Read access SB.5 Reg. no. Number of the register that was read or written. SB.0 KL2819 Version: 1.0.0...
Access from the user programm Register description Die folgenden Register dienen zur Parametrierung der KL2819. Sie können mit Hilfe von Control-, Status- und Daten-Bytes über die Registerkommunikation ausgelesen oder beschrieben werden. R8: Terminal description Register R8 contains the designation of the KL2819 terminal: 0x0B03 (2819 R9: Firmware version Register R9 contains the ASCII coding of the terminal's firmware version, e.g.
Beckhoff's branch offices and representatives Please contact your Beckhoff branch office or representative for local support and service on Beckhoff products! The addresses of Beckhoff's branch offices and representatives round the world can be found on her internet pages: http://www.beckhoff.com You will also find further documentation for Beckhoff components there.
Page 31
List of illustrations List of illustrations Fig. 1 KL2819 ............................Fig. 2 Overload current limitation......................Fig. 3 Schematic illustration of the thermal switch-off in case of overload ..........Fig. 4 Switch-off of inductive loads ......................Fig. 5 Attaching on mounting rail ......................