Error handling and diagnosis
LEDs for K-bus diagnostics
Error code
Error code argu-
ment
Persistent,
continuous flashing
1 pulse
0
1
2
2 pulses
0
n (n > 0)
3 pulses
0
4 pulses
0
n
5 pulses
n
6 pulses
0
1
4
8
16
14 pulses
n
15 pulses
n
16 pulses
n
42
Description
Remedy
EMC problems
• Check power supply for undervoltage or
• Implement EMC measures
• If a K-bus error is present, it can be
EEPROM checksum
Set manufacturer's settings with the KS2000
error
configuration software
Code buffer overflow
Insert fewer Bus Terminals. Too many
entries in the table for the programmed
configuration
Unknown data type
Software update required for the Bus
Coupler
Programmed
Check programmed configuration for
configuration has an
correctness
incorrect table entry
Table comparison
Incorrect table entry
(Bus Terminal n)
K-bus command error • No Bus Terminal inserted
• One of the Bus Terminals is defective;
K-bus data error,
Check whether the n+1 Bus Terminal is
break behind the Bus
correctly connected; replace if necessary.
Coupler
Break behind Bus
Check whether the bus end terminal 9010 is
Terminal n
connected.
K-bus error in register
Exchange the n
communication with
Bus Terminal n
Error at initialization
Exchange Bus Coupler
Internal data error
Perform a hardware reset on the Bus
Coupler (switch off and on again)
DIP switch incorrect
Set 1-8 to on or off, see BootP
for BootP
Internal data error
Perform a hardware reset on the Bus
Coupler (switch off and on again)
Error in IP socket
Perform a hardware reset on the Bus
Coupler (switch off and on again)
th
n
Bus Terminal has
Start the Bus Coupler again, and if the error
the wrong format
occurs again then exchange the Bus
Terminal
Number of Bus
Start the Bus Coupler again. If the error
Terminals is no longer
occurs again, restore the manufacturers
correct
setting using the KS2000 configuration
software
Length of the K-bus
Start the Bus Coupler again. If the error
data is no longer
occurs again, restore the manufacturers
correct
setting using the KS2000 configuration
software
Version: 2.3.0
overvoltage peaks
localized by a restart of the coupler (by
switching it off and then on again)
halve the number of Bus Terminals
attached and check whether the error is
still present with the remaining Bus
Terminals. Repeat until the defective Bus
Terminal is located.
th
bus terminal
BK9053, BK9103