Maintenance / Repair
7

Status query

7.1 Status query

7.2 Performance check

38 | 50
7 Maintenance / Repair
Check the detector on a regular basis, but at least once a year.
To do this, look for/check the following and resolve any problems you identify:
Mechanical damage
Soiling
Correct fastening
Detector function by means of test activation
The query is issued from the control panel, via the radio gateway.
The following queries may be issued:
Danger level
Detector fault
Radio status
Depending on the authorization level of the user and the control panel type, the
following actions can be performed:
Device test (Go/No Go or detailed by status polling)
Activation of a test alarm
Reading out the identification number, customer text and measure text
Localizing and setting the parameters of the detector
Switching off the detector
See also
2
2
The selftest automatically subjects the detectors to an extensive electrical
performance check. Regular performance checks of the detectors are required
nonetheless. These can be performed using test gas or hot air.
Recommendation:
Perform a visual inspection on all detectors every year. Detectors that are
heavily soiled or mechanically damaged must be replaced.
All detectors should be replaced after 6 to 8 years of service, depending on the
ambient conditions.
Diagnosis levels [➙ 18]
Internal alarm indicator [➙ 19]