Modulex EXT Commercial Series Boilers User Manual
CHAPTER 6: Operation of the E8 Controller
TABLE 6-6: EXPERT Menu - Continued
LEVEL
HTG CIRCUIT 1/2
HC FUNCTION
PUMP MODE
MIXER OPEN
MIXER CLOSE
MAX T-FLOW
MIN T-FLOW
T-FROST PROT
OUT-TEMP-DEL
SLOPE OFFSET
B-HEAT SINK
RETURN
SOLAR / MF
RELAY FUNC 1 to 4
T-MF1 to 4 SETP
MF 1 to 4 HYST
FUNZ. F15
RETURN
NOTES:
There is another sub-menu under the EXPERT menu called EXPERT HS. See section 4.35
– High Altitude Adjustment for details.
Some menus are visible only if the relevant sensor is wired.

6.10 OTHER POSSIBLE SETTINGS

6.10.1 Settings for Heating Circuit 1/2

6.10.1.1

Heating Adjustment With Constant Flow Temp

(Without Outer Sensor)
Offers the possibility to have a constant flow temperature on the selected heating circuit.
INSTALLATION menu >
6.10.1.2

Temperature Settings For Heating Circuits

(Only After Function Selection)
USER menu
USER menu
Page 106 of 144
09/15/2017
DESCRIPTION
Heating circuit function selection
Pump operating mode
Open mixer dynamic
Close mixer dynamic
Max flow temperature setting
Min flow temperature setting
Frost protection temperature
Ouside temperature delay
Heating slope distance
Circuit enable
Function selection relay 1 to 4
Switching temperature relay MF1 to 4
Hysteresys relay MF1 to 4
Sersor function F15
HC FUNC "01"
Heating circuit I / II
Heating circuit I / II
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Phone: 800-526-0288
00
18
12
176
10
32
86
FLOW TEMP DAY
FLOW TEMP NIGHT
ENTRY
0
(00 ÷ 04)
(00 ÷ 03)
(5 ÷ 25)
(5 ÷ 25)
(68 ÷ 230)
(50 ÷ 230)
(5 ÷ 41)
0
(0 ÷ 24)
9
(0 ÷ 90)
0
(00 ÷ 01)
0
(00 ÷ 26)
(86 ÷ 194)
9
(4 ÷ 18)
0
(00 ÷ 02)
OMM-0095_0H
GF-139