Operation manual
9.1.2
G9SR-BC wiring without dynamic testing with EDM
Function setting:
DIP Switch 1 OFF
DIP Switch 2 OFF
DIP Switch 3 ON
Description:
E-Stop pushbutton connected to T12 and T22
Restart pushbutton connected to T31
KM1 and KM2: Motor Contactors
Feedback loop (EDM) connected to T32
Remarks:
Applicable up to PLd acc. EN ISO 13849-1
Motor circuit (contacts of KM1 and KM2) not shown.
+24V
Fuse
5A F
OV
Figure 6 - G9SR-BC wiring without dynamic testing with EDM
= Manual Restart
= Dynamic input testing Disabled
= EDM Enabled
A1
T11
T12
T21
Safety
Power
Input 1
Input 2
supply
Safety Output
circuit
Control
A2
14
KM1
T22
T31
Safety
Restart
Auxiliary Output
Control
24
44
KM2
KM1
KM2
T32
EDM
G9SR
Page 41 of 79