Dip Switches And Functions Of G9Sr-Bc - Omron G9SR Series Operation Manual

Safety relays
Hide thumbs Also See for G9SR Series:
Table of Contents

Advertisement

Operation manual
6.3
Dip switches and functions of G9SR-BC□-□
The DIP-Switches are used to configure the G9SR-BC unit for the
application.
There are two banks of DIP-switches in the G9SR-BC.
Both DIP-switch banks have eight switches.
To select a function, the switches on both DIP-switch banks
have to be set identically.
Example:
DIP SWITCH 3, BANK1 = "OFF"
and
DIP SWITCH 3, BANK2 = "OFF" => OK
DIP SWITCH 3, BANK1 = "OFF"
and
DIP SWITCH 3, BANK2 = "ON" => ERROR
!
Caution
Use the switches to configure following functions:
Function
Restart
Dynamic Input Testing
EDM
INPUT LOOP
AUX OUT STATUS
Page 20 of 79
Do not change the setting of the DIP switches during operation of
the G9SR-BC. In this case, the G9SR-BC will change the outputs
to "OFF" and will enter a lockout state.
Switch
G9SR-BC□-□
1
ON =
OFF = Manual Restart
2
ON =
OFF =
3
ON =
OFF =
4
ON = input loop enabled.
OFF = input loop disabled
5
ON = Aux out status consistent with OSSD
OFF = Aux out status inverted.
6/7/8
Reserved
Auto Restart
Enabled
Disabled
Enabled
Disabled
This disables the OSSDs and Aux out.
G9SR
ON
1
2
3
4
5
6
7
8
ON
1
2
3
4
5
6
7
8