Dip Switch Functions - Omron K8DT-TH Manual

Temperature monitoring relay
Table of Contents

Advertisement

DIP Switch Functions

K8DT-TH1
R_SW3
100°C/°F units (0 to 9)
R_SW2
10°C/°F units (0 to 9)
R_SW1
1°C/°F units (0 to 9)
Note: The default setting is 0°C.
ON ❍↑
PIN
OFF ●↓
Upper limit
Alarm Mode
Lower limit
With latching
Latching
Without latching
Normally open
Output drive
method
Normally closed
°C
Temperature
unit
°F
K
J
T
E
Input type
Pt100
Pt1000
NOT USE
NOT USE
Note: All pins are set to OFF by default.
K8DT-TH2
1,000°C/°F units (0 to 3)
R_SW3
Note: A temperature setting error occurs if this switch
is set to a value from 4 to 9.
R_SW2
100°C/°F units (0 to 9)
R_SW1
10°C/°F units (0 to 9)
Note: The default setting is 0°C.
ON ❍↑
PIN
OFF ●↓
Upper limit
Alarm Mode
Lower limit
With latching
Latching
Without latching
Normally open
Output drive
method
Normally closed
°C
Temperature
unit
°F
K
J
T
E
Input type
B
R
S
PL II
Note: All pins are set to OFF by default.
1
2
3
ON
OFF
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
1
2
3
ON
OFF
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
4
5
6
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
4
5
6
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
K8DT-TH
7
8
---
---
---
---
---
---
---
---
Not used.
7
8
---
---
---
---
---
---
---
---
Not used.