General Specification - Toshiba nv Series Instruction Manual

Light controller unit
Hide thumbs Also See for nv Series:
Table of Contents

Advertisement

Appendix A Specification
A.1

General Specification

Operating ambient
temperature
Storage temperature
Operating ambient
relative humidity
Dust
Pollution level
Corrosive gas
Operating altitude
Resistance to vibration
(vibration immunity)
mpact resistance
(impact immunity)
Insulation resistance
Dielectric strength
Free fall
Noise immunity
EMC zone
Ground
Structure
Installation site
Cooling system
Weight
Outside dimensions
Standard satisfied
Expected useful life
88
6F8C1575
Table A-1 General specification
Item
0°C to 55°C; 40°C or less on average over 24 hours
-40 to 70°C
10% to 95%RH, Level RH2 (no condensation)
Dust 0.3 mg/m
(no conductive dust permitted)
2 (usually no conductive pollution) or less
No corrosive gas permitted.
No silicone-containing material permitted.
2,000 m or less
IEC 60068-2-6, test Fc compatible, X, Y, Z
10 cycles each
IEC 60068-2-27, test Ea compatible 147 m /s
(3 orthogonal axes, 3 times each)
500 VDC Mega 10 MΩ or more
2,000 VAC 1 min
Shipping package: 1,000 mm
For product package: 300 mm
Fast transient
AC power: 2 kV
DC power: 2 kV (section of 10 m or less is
unnecessary)
I/O power DC: 1kV (section of 10 m or less is
unnecessary)
AC-I/O: 2 kV (unshielded cable)
DC-I/O: 1 kV (unshielded cable)
Analog I/O: 1 kV (unshielded cable)
4 kV (contact discharge) Level ESD-3
Electrostatic
discharge
10 V/m
Radiated
electromagnetic field
Impulse noise
Power wire Noise voltage: 1,500 V
Pulse width: 1μs/100 ns
Zone B (including Zone A)
Category D Ground
Open type Component
In indoor control board
Nature air cooling
Approx. 4kg BUM22 (duplexed chassis, full slot
installed)
Base unit with controller, power module and
interface module:416.5 (W) x 135 (H) x 115 (D)
IEC61131-2, JIS B 3502
CE marking
UL508
10 years: Controller, base unit, transmitter
(operating ambient temperature: 40C, when
natural air cooling is used)
Specification
3
2
Remarks
(Note 1)
(Note 2)
IEC 61131-2
(Note 3)
(Note 4)
Between Power and GND
Terminals
I/O: Refer to the Individual
Specification.
Between Power and GND
terminals
I/O: Refer to the Individual
Specification.
(Note 5)
Excluding
protrusions
Maintenance parts
need to be replaced.
(Note 6)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Type2

Table of Contents