Fault Conditions and Recommended Corrective Actions

Table 12: Fault Conditions and Recommended Corrective Actions.

Condition
Blank display
Critical diagnostic
display
Offline status display
24
RMA805 Enraf FlexLine Remote Indicator User's manual
Analysis
The Remote Indicator has no power
The environmental temperature is
o
below -20
C or above + 50
Something went wrong.
The FlexLine Gauge is still starting
up
The FlexLine Gauge did not
recognize the Remote Indicator
because of a communication issue
during initialization.
The Remote Indicator does not
receive new data from the Flexline
Gauge.
Recommended/Corrective
Action
Check that the gauge the
Remote Indicator is connected
to is powered on and working
correctly.
Check the cable to assure it is
not damaged.
Check that the wires are
connected correctly at the
terminals
Check that the wires are
connected to the right
terminals.
Check that the Failsafe
Jumper is set to Downscale.
The LCD display may turn
o
C
blank below -20°C and above
70°C (-4°F and 158°F). The
display will again be readable
when temperatures return to
within operable limits.
Replace the Remote Indicator
Please wait until the
initialization has completed
Please reset the FlexLine
Gauge
Reset the FlexLine Gauge.
Check to assure the cable is
not damaged.
Check that the wires are
connected correctly at the
terminals
Revision 1