3.3.2

Device Setup Menu

FlexLine Gauges are capable of driving 2 displays at the same time. However only 1 display can
be showing actual data. Each device must have a different HART address. Only HART address 7
or 8 is allowed.
Each display can be activated by pressing a button. After pressing a button on the Hart SmartView
or the Remote Indicator that device will go online and become the active display showing the
actual data, automatically causing the other display to go into Standby mode.
Since the buttons on the Remote Indicator are not easily accessible there is an option to make it
automatically become active by configuring a standby wait time. When this setting is > 0 the
device will automatically go online after the programmed waiting time.
<Return> Return to the Level 1 menu
<Return>
HART Address
Parameters
Standby Time
3.3.3

Information Menu

<Return> Return to the Level 1 menu
<Return>
Display
Firmware Version
<Return>
Comm
Module
Firmware Version
14
RMA805 Enraf FlexLine Remote Indicator User's manual

Table 5: Device Setup Menu

7 or 8
HART polling address
Default: 7
Enter the time in
minutes until the device
automatically goes
0 – 15
online once in standby.
Default: 5
0 means the device
does NOT automatically
go online.

Table 6: Information Menu

The firmware version of the Display Module
The firmware version of the Communication
Module
Press
to edit,
↑ or ↓ to select
number and
to
enter.
Press
to edit,
↑ or ↓ to select
number and
to enter.
Read Only
Read Only
Revision 1