MA-1000
6.2.4 General Fault relay
The General Fault relay is usually in energized state and volt-free /
potential-free. It is de-energized in Fault condition.
Contact range: max 30 V AC / DC, 1 A, non-inductive loads.
Settings: NO contact (Jumper JGST).
6.2.5 General Alarm relay
The General Alarm relay is usually in energized state and volt-free /
potential-free. It is de-energized in Fire condition.
Contact range: max 30 V AC / DC, 1 A, non-inductive loads.
Settings: NO contact (Jumper JALL)
Polarized devices balanced with resistor (electronic Sounders, etc.)
xx
xx
Polarized devices balanced with diode (electronic Sounders, etc.)
xx
xx
Non-polarized devices balanced with a resistor (Bells, relays, etc.)
xx
xx
22
47 K
¼ W
1N4004
47 K
¼ W
Main Fault output connections
(refer to basic board topography)
Main Alarm output connections
(refer to basic board topography)
2 x 1N 4004
CNU
21 22
COM NO/NC
CNU
13 14
COM NO/NC
Connect the
, ¼ W
47 KΩ
EOL resistor or the diode
only on last sounder of
the line.
Polarity displayed are in
Alarm condition, at idle
condition, they are
inverted!
M-167.1-MA1000-EN / 02.2023