Fixed Outputs - Dry Contacts; Description; Position Auxiliary Contact; Atys R Product Available Output (Motorisation) - socomec ATyS Instruction Manual

Remote transfer switching equipment
Hide thumbs Also See for ATyS:
Table of Contents

Advertisement

8.2.3. Fixed outputs - Dry contacts

8.2.3.1. Description

As standard, the ATyS risequippedwithfourfixedoutputslocatedonthe
motorisation module.
(Drycontactstobepoweredbytheuser).

8.2.3.2. Position auxiliary contact

The ATyS risequippedwithintegratedposition(I–O–II)auxiliarycontactoutputsthrough3offmicroswitches.
Pins 13, 04, 14, 24
(NormallyOpencontactswithpin13ascommon)
8.2.3.3. ATyS r Product available output (motorisation)
Pin 63A – 64A
(NormallyOpencontactthatisheldclosedwhenthemotorisationisavailable).
Thiscontactgivesconstantfeedbackabouttheproduct'savailabilityandit'scapacitytotransferfromthemainsupplytothe
alternative.ThefeedbackgivenisrelativetothemotorisationmoduleexcludingtheATScontrollerthatmaybemonitored
separately.
The ATyS rperformsaselfdiagnosticstestonthemotorisationmoduleatstartup,whenputfromManual->Autoandthen
every 5 minutes. This test ensures that the ATyS risoperationalintermsofcontrolinputs.Shouldoneofthetestsfail,a
secondtestisperformedtoreconfirmtheerrorstate.ShouldtheATyS rmotorisationmodulebecomeunavailable,contact
63A–64Aareopened,thepower/readyLED'sareswitchedoff,andthefaultLEDisactivated.ThefaultLEDwillremain
activeforaslongassufficientpowerisavailableandthefaultconditionisnotreset.Thefaultisresetwhentheproductis
switched from AUT -> Manual -> Auto mode.
ATyS r(Motorisation)ProductAvailable/UnavailableWatchdogrelaywillopenforanyofthefollowingreasonsbelow:For
addedsecurity,"ProductAvailability"isinformativeanddoesnotnecessarilyinhibitmotoroperation.
ProductUnavailable+WarningLEDCondition:
Product in manual mode
Motornotdetected(Autotest)
Control voltage out of range
Operatingfactorfaultactive(N°ofoperations/min)
Powerfail active
Customer input autotest failed
Invalid product customisation
Abnormal switching when not in manual mode
Requested position not reached
Locked mode active when not in manual mode
ExternalFault->Userinput
Unexpectedcurrentflowingthroughthemotorwhenidle
Sampling rate for the above is every 10 ms
Exception: motor detection sampling rate is every 5 min
ATyS / ATyS r - 541630C - SOCOMEC
Inhibition
Yes
No
Yes
Yes
Yes
No
No
Yes
Yes
Yes
No
Yes
39