4.2. Quick Start ATyS r Frame B6 to B8 (800A to 3200A)
549614D
QUICK START
EN
ATyS / ATyS
Motorised Source Changeover Switch
Preliminary operations
Check the following upon delivery and after removal of the
packaging:
- Packaging and contents are in good condition.
- The product reference corresponds to the order.
- Contents should include:
Qty 1 x ATyS / ATyS r
Qty 1 x Emergency handle and fixing clip
Quick Start instruction sheet
Warning
Risk of electrocution, burns or injury to persons and /
or damage to equipment.
This Quick Start is intended for personnel trained in the
installation and commissioning of this product. For further
details refer to the product instruction manual available on
the SOCOMEC website.
• This product must always be installed and
commissioned by qualified and approved personnel.
• Maintenance and servicing operations should be
performed by trained and authorised personnel.
• Do not handle any control or power cables connected to
the product when voltage may be, or may become
present on the product, directly through the mains or
indirectly through external circuits.
• Always use an appropriate voltage detection device to
confirm the absence of voltage.
• Ensure that no metal objects are allowed to fall in the
cabinet (risk of electrical arcing).
- For 800 - 3200 A (Uimp = 12 kV). Terminations must respect
a minimum of 14 mm clearance from live parts to parts
intended to be earthed and between poles.
Failure to observe good enginering practises as well as to
follow these safety instructions may expose the user and
others to serious injury or death.
Risk of damaging the device
In case the product is dropped or damaged in any way it is
recommended to replace the complete product.
Accessories
• Bridging bars and connection kits.
• Control voltage transformer (400 VAC
• DC power supply (12/24 VDC
• Phase barriers.
• Terminal shrouds.
• Terminal screens.
• Auxiliary contacts (Additional).
• Padlocking in 3 positions (I - O - II).
• Lockout accessories (RONIS - EL 11 AP).
• Door escutcheon frame.
• ATS controller ATyS C25.
• ATS controller ATyS C55 or C65.
For further details refer to the product instruction manual
under chapter "Spares and Accessories"
www.socomec.com
To download, brochures, catalogues
and technical manuals:
https://www.socomec.com/
operating-instructions_en.html
12
EN
Installation and Commissioning
STEP 1
800 A - 3200 A
Cabinet / Back Plate
Installation
r
STEP 1
STEP 1
1
230 VAC).
230 VAC).
Caution: ensure that the
product is installed on a
flat rigid surface.
STEP 2
To be connected using terminal lugs, rigid or flexable busbars.
Minimum cable section Cu (mm
Recommended cable section Cu (mm
Maximum Cu cable cross-section (mm
Maximum Cu busbar width (mm)
Type of screw
Recommended tightening torque (lb.in/N.m)
Maximum tightening torque (lb.in/N.m)
STEP 2
STEP 3
Connecting the
COMMAND /
Power SUPPLY
POWER section
CONTROL terminal
connections
connections
Clip for
storage of
the
emergency
handle
Installation
Recommended
OK
orientation
Power Terminal Connections
FRAME B6
800 A
2
)
2x185
2
)
2x50x5
2
)
4x185
63
M8
73.46/8.3 73.46/8.3 177.02/20
115.06/13 115.06/13 230.13/26
STEP 6A
Control by an external
order (AUTO)
STEP 4
STEP 5
STEP 6B
CHECK
Emergency Manual
terminal
Operation
STEP 6C
Padlocking
2
M8 Type Z
M8
OK
FRAME B7
FRAME B8
1000 A
1250 A
1600 A
2000 A
-
-
-
-
2x63x5
2x63x7
2x100x5
3x100x5 2x100x10 3x100x10
4x185
4x185
6x185
-
63
63
100
100
M8
M10
M12
M12
354.04/40
354.04/40 354.04/40 354.04/40
398.30/45
398.30/45 398.30/45 398.30/45
ATyS / ATyS r - 541630C - SOCOMEC
2500 A
3200 A
-
-
-
-
100
100
M12
M12