Installation and Commissioning
QUICK START
}}$ 3
EN
STEP 1
ATyS
d
M
Cabinet / Back
Plate Installation
Remotely operated
Transfer Switching Equipment
Preliminary operations
Check the following upon delivery and after removal of the
packaging:
n
Packaging and contents are in good condition.
n
The product reference corresponds to the order.
n
Contents should include:
Qty 1 x ATyS M
Qty 1 x Emergency handle extension rod
Qty 1 x Set of terminals
Quick Start instruction sheet
Warning
Risk of electrocution, burns or injury to persons and /
or damage to equipment.
This Quick Start is intended for personnel trained in the
installation and commissioning of this product. For further
details refer to the product instruction manual available on
the SOCOMEC website.
n
This product must always be installed and commissioned
by qualified and approved personnel.
n
Maintenance and servicing operations should be
performed by trained and authorised personnel.
n
Do not handle any control or power cables connected to
the product when voltage may be, or may become present
on the product, directly through the mains or indirectly
through external circuits.
n
Always use an appropriate voltage detection device to
confirm the absence of voltage.
n
Ensure that no metal objects are allowed to fall in the
cabinet (risk of electrical arcing).
Failure to observe good enginering practises as well as to
follow these safety instructions may expose the user and
others to serious injury or death.
Risk of damaging the device
n
In case the product is dropped or damaged in any way it
is recommended to replace the complete product.
STEP 5B
Accessories
n
Bridging bars and 125A or 160A.
Open the front cover as
shown to put into manual
n
Voltage sensine and power supply TAP.
mode.
n
Terminal shrouds.
Use the handle situated in
n
Additionnal aux contact block.
the front panel under the cover to operate the
n
Plastic enclosure.
transfer switch.
n
Dual Power Supply (DPS).
Check the changeover switch position on the
n
Power Connection Terminals.
indicator before operating.
n
ATS Control relay ATyS C30 + D10 or D20.
n
ATS control relay ATyS C20.
90º
n
ATS control relay ATyS C40.
To simplify operation
use the handle with the
extension provided.
STEP 5C
In order to padlock put the
product in manual mode.
Pull the locking mecha-
nism and insert a padlock
as shown.
As standard padlocking in the 0 position.
www.socomec.com
Configurable to I-0-II (see step 1).
www.socomec.com/en/atys-d-m
To download, brochures, catalogues and technical manuals.
Printing informations: 1 color Black. White paper 90g/m
2
.
Printing size: 420x297. Final size 210x297. This page visible first.
A separate sheet for each language.
Non contractual document.
542 954 B - 06/14 - EN
Subject to change without notice.
STEP 5A
Automatic Operation
STEP 2
STEP 3
STEP 4
STEP 5B
Connecting the
CONTROL /
CHECK
Emergency Manual
POWER section
AUX POWER
Operation
terminal
connections
STEP 5C
Padlocking
STEP 4
Manual operation
Check
Whilst in manual mode, check the wiring and
LIbRN SRZHU XS WKHbSURGXFW
STEP 5A
90º
Automatic operation
Extension
Close the front cover as shown to put the product
into automatic mode. The product is now ready to
receive order inputs based on the following logic.
Impulse logic
(Max 8 Nm)
order I
order 0
Padlocking mode
order II
position I
position 0
position II
,PS PV
Note: Excludes position switching delays.
For contactor logic bridge
contact 313 with 317.
To operate: close the
contact corresponding to
the desired position.
1x 4-8 mm
STEP 1
Installation
Caution: Ensure that the product is installed on a flat rigid surface.
Recommended orientation
Recommended
Ok
DIN RAIL
IEC 60715
STEP 2
Power Terminal Connections
It is essential to tighten
DOObWHUPLQDOV LQFOXGLQJ
WKRVHbQRW EHLQJ XVHG
Source supply side
STEP 3
CONTROL / AUX POWER
Terminals and wiring
Ensure that the product is in Manual Mode (front cover open).
6 mm
Contactor logic
Auxiliary contacts:
One module factory fitted (1309 0001).
1309 0001 or 1309 0011
Fitting of the 2nd AC:
To fit an AC, the switch must first be put in position 0. An auxiliary contact module comprises: one NO/
NC changeover contact for each position (I-0-II). To install use the long screws supplied with the module.
maintened
Use 35mm
screws for
2 modules
13
Ok
Ok
Ok
Ok
46
53
73,5
Tighten to avoid
PRYHPHQWbRQbWKH ',1bUDLO
Posidriv PZ1
1 Nm
9ROWDJH WDSV SURYLGH [ PP
They can be fitted in any terminals on the source
supply side. Do not use on the load side when
equipped with a bridging bar.
Load side
bridging bar.
125A: 1309 2006
160A: 1309 2016
Hexagonal Metric
Allen size 4
5,0 Nm
10 to
70 mm²
15mm
!
X4
Type
Terminal no.
Description
Inputs
101 / 102
Source 1 power supply
201 / 202
Source 2 power supply
0,5 to 2,5 mm²
313
Position 0 order if closed with 317.
Also allows control logic selection: contactor
0,5 to 1,5 mm²
(always closed) / impulse (close to switch)
314
Position II order if closed with 317
Slotted head 3mm 0,5 Nm
315
Position I order if closed with 317
317
Common control terminal for 313 to 315
Auxiliary
11/12/14
Position I
contacts
21/22/24
Position II
unit.
01/02/04
Position 0
Control of position I and II have priority on control of position 0.
LOAD
A
B
B
317
315
314
313
202
201
102
101
6
6
1
3
2
5
4
Pozidriv PZ2 - 1 Nm
235
Padlocking configuration
222
116
The ATyS M is delivered with
26
padlocking configured to the
18
O position.
MAX : 2
235
52
176
224
Posidriv PZ2
To allow padlocking in all
positions (I - O - II), configure
WKH $7\6b0 DV IROORZV EHIRUH
4 mounting brackets
installation. (Screw is located
4x M6 screw - 2,5 Nm
at the back of the product).
STEP 1
2
connections.
Posidriv PZ2
2x
2
Posidriv PZ2
STEP 2
STEP 3
2x
Slotted head 3,5 mm
0,45 Nm
0,5 to 2,5 mm²
Posidriv PZ2
2,2 lb-in 0,25 Nm
0,5 to 1,5 mm²
6 mm
Recommanded
Characteristics
connection
cross-section
220Vac -20% (176Vac) to 240Vac
+20% (288Vac) 45 to 65Hz
0,5 to 2,5 mm²
(rigid)
Do not connect to any power supply
0,5 to 1,5mm²
(stranded)
Dry potential free contact
250Vac 5A AC1
24Vdc 2A
1: Position I order
2: Position II order
3: Position 0 order
4: Power supply I (230 VAC)
5 A AC1
5 A AC1
250 Vac
250 Vac
5: Power supply II (230 VAC)
22 24 21
22 24 21
6: Voltage tap
7: Auxiliary contact block -
1 NO/NC contact per position I,
0, II (1x factory fitted)
7
11 14 12
11 14 12
A: Bridging bar (accessory)
01 04 02
01 04 02
1309 0001
1309 0011
B: Single-phase voltage sensing tap
(accessory)
C: F1/F2 = fuse 10 A gG
C
* Remote orders from ATS
controller such as ATyS C20/
C30/C40 or PLC, BMS, etc.