Environmental; Ip Rating; Operating Conditions; Temperature - socomec ATyS Instruction Manual

Remote transfer switching equipment
Hide thumbs Also See for ATyS:
Table of Contents

Advertisement

5.3. Environmental

The ATyS rproductmeetsthefollowingenvironmentalrequirements:

5.3.1. IP Rating

• IP2XagainstdirectcontactfortheATyS rmotorizationcontrolunit.
ø 1 mm
• IP2X against direct contact for the power section with the connections in place and when including
suitable, correctly installed incoming and outgoing terminal shields.
• IP 0 for the bare power section without terminal shields in place.

5.3.2. Operating Conditions

5.3.2.1. Temperature

• From -20 to +40°C without derating
• From -20 to +70°C when applying a Kt derating correction factor
Kt: Correction Factor
*Simplifiedderatingmethod:Ithu≤IthxKf
* A moreprecisecalculationmaybedoneforspecificapplications.Shouldthisberequiredpleasecontact
SOCOMEC.

5.3.2.2. Hygrometry

• 80%humiditywithoutcondensationat55°C
• 95%humiditywithoutcondensationat40°C

5.3.2.3. Altitude

• Up to 2000m in altitude without derating
• For higher altitude the Ka correction factors below apply
Ka: Correction Factor
Ue
Ie

5.3.3. Storage Conditions

5.3.3.1. Temperature
• From -40 to +70°C
16
EN
Temperature
0.9
40°C...50°C
0.8
50°C...60°C
0.7
60°C...70°C
2000 m < A ≤ 3000 m
0.95
0.85
3000 m < A ≤ 4000 m
0.8
0.85
ATyS / ATyS r - 541630C - SOCOMEC

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents