Installation and Commissioning
QUICK START
}}$ 3
EN
ATyS
t
M
STEP 1
Cabinet / Back
Plate Installation
Automatic
Transfer Switching Equipment
Preliminary operations
Check the following upon delivery and after removal of the
packaging:
■
Packaging and contents are in good condition.
■
The product reference corresponds to the order.
■
Contents should include:
Qty 1 x ATyS M
Qty 1 x Emergency handle extension rod
Qty 1 x Set of terminals
Quick Start instruction sheet
Warning
Risk of electrocution, burns or injury to persons and /
or damage to equipment.
This Quick Start is intended for personnel trained in the
installation and commissioning of this product. For further
details refer to the product instruction manual available on
the SOCOMEC website.
■
This product must always be installed and commissioned
by qualified and approved personnel.
■
Maintenance and servicing operations should be
performed by trained and authorised personnel.
■
Do not handle any control or power cables connected to
the product when voltage may be, or may become present
on the product, directly through the mains or indirectly
through external circuits.
■
Always use an appropriate voltage detection device to
confirm the absence of voltage.
■
Ensure that no metal objects are allowed to fall in the
cabinet (risk of electrical arcing).
STEP 6A
Failure to observe good enginering practises as well as to
follow these safety instructions may expose the user and
Close the front cover as
others to serious injury or death.
shown to put the product
into automatic mode.
Risk of damaging the device
■
In case the product is dropped or damaged in any way it
is recommended to replace the complete product.
STEP 6B
Accessories
Open the front cover as
■
Bridging bars 125A or 160A.
shown to put into manual
■
Control voltage transformer (400Vac -> 230Vac).
mode.
■
Use the handle situated in
Voltage sensing and power supply tap.
the front panel under the cover to operate the
■
Terminal shrouds.
transfer switch.
■
Auxilliary contact blocks.
Check the changeover switch position on the
■
Polycarbonate enclosure.
indicator before operating.
■
Polycarbonate extension box.
■
Power Connection Terminals.
90º
■
Sealable cover.
To simplify operation
use the handle with the
extension provided.
STEP 6C
In order to padlock put the
product in manual mode.
Pull the locking mecha-
nism and insert a padlock
as shown.
As standard padlocking in the 0 position.
www.socomec.com
Configurable to I-0-II (see step 1).
www.socomec.com/en/atys-t-m
To download, brochures, catalogues and technical manuals.
Printing informations: 1 color Black. White paper 90g/m
2
.
Printing size: 420x297. Final size 210x297. This page visible first.
A separate sheet for each language.
Non contractual document.
542 930 B - 06/14 - EN
Subject to change without notice.
STEP 2
STEP 3
STEP 4
STEP 5
Connecting the
CONTROL /
CHECK
Programming
POWER section
AUX POWER
terminal
connections
Automatic
operation
STEP 4
Manual operation
Check
Whilst in manual mode, check
the wiring and if ok power up
the product.
STEP 5
Programming
■ Auto conf. of the network voltage and frequency.
90º
Extension
Setting mode A-B
A: Ready
B: Auto Conf
(Auto-configuration)
1. Put dipswitch A-B to
position B. (All Led's
should be blinking).
(Max 8 Nm)
2. When the LED's
become a steady light
ON, confi guration of
Padlocking mode
the network is ready.
3. Put dipswitch A-B
back to A.
■ Set dip switches C-D, E-F, G-H
Thresholds C-D
& 8 )
' 8 )
HYST: 20 % of 6U/F settings
1x 4-8 mm
STEP 6A
STEP 1
Installation
Automatic Operation
Caution: Ensure that the product is installed on a flat rigid surface.
Recommended orientation
STEP 6B
Emergency Manual
Operation
STEP 6C
Recommended
Ok
Padlocking
DIN RAIL
IEC 60715
STEP 2
Power Terminal Connections
It is essential to tighten
DOObWHUPLQDOV LQFOXGLQJ
WKRVHbQRW EHLQJ XVHG
Source supply side
STEP 3
CONTROL / AUX POWER Terminals and wiring
LOAD
2
2
4
4
6
6
8
8
2
2
4
4
6
6
8
8
1
1
3
3
5
5
7
7
1
1
3
3
5
5
7
7
O1
207208 209 210 63 64 73 74
I1 I2 I3
not used
■ Set potentiometer for priority
supply "Failure and Return Timer"
FT: 0-30 sec / RT: 0-30 min.
Stop in 0 position E-F
E: No stop in O position
F: 2s stop in 0 position
Priority G-H
G: With priority
H: Without priority
Ok
Ok
Ok
Ok
46
53
73,5
Tighten to avoid
PRYHPHQWbRQbWKH ',1bUDLO
52
6 mounting brackets
Posidriv PZ1
1 Nm
6x M6 screw - 2,5 Nm
9ROWDJH WDSV SURYLGH [ PP
They can be fitted in any terminals on the source
supply side. Do not use on the load side when
equipped with a bridging bar.
Load side
bridging bar.
125A: 1309 4006
160A: 1309 4016
Hexagonal Metric
Allen size 4
m
2
5,0 Nm
WG
m
2
*
WG
10 to
70 mm²
15mm
8
Ensure that the product is in Manual Mode
(front cover open).
Recommanded
Type Terminal
Characte-
Description
connection
no.
ristics
cross-section
5 A AC1
250 Vac
Inputs
207
Common
22 24 21
208
Position 0 order
Open SI priority.
209
Closed S2
Do not
11 14 12
priority.
connect to
210
Inhibition ATS
any power
01 04 02
0,5 to 2,5 mm²
supply
1309 0001
Outputs
Open: SI and S2
(rigid)
NOT available.
5 A AC1
63/64
250 Vac
Closed: SI or S2
0,5 to 1,5mm²
22 24 21
available
(stranded)
73/74
Not used
Auxiliary
11/12/14 Position I
Dry
contacts
potential
11 14 12
21/22/24 Position II
unit.
IUHHbFRQWDFW
250Vac 5A
01 04 02
01/02/04 Position 0
1309 0011
AC1
24Vdc 2A
Auxiliary contacts:
To fit an AC, the switch must first be put in position 0. An auxiliary contact module comprises: one
NO/NC changeover contact for each position (I-0-II). To install use the long screws supplied with
the module.
■ Source availability LED's
Source
LED ON Source 1
Source 2
available
available
LED OFF Source 1 not
Source 2 not
availlable
availlable
- a timer is
- a timer is
LED
counting
counting
blinking
down
down
340
Padlocking configuration
324
116
The ATyS M is delivered with
13
26
padlocking configured to the
18
O position.
MAX : 2
340
326
104
176
Posidriv PZ2
To allow padlocking in all
positions (I - O - II), configure
WKH $7\6b0 DV IROORZV EHIRUH
installation. (Screw is located
at the back of the product).
Step 1
2
connections.
Posidriv PZ2
2x
2
Posidriv PZ2
Step 2
Step 3
STEP 3
2x
Slotted head 3,5 mm
0,45 Nm
0,5 to 2,5 mm²
Posidriv PZ2
2,2 lb-in 0,25 Nm
0,5 to 1,5 mm²
6 mm
0,5 to 2,5 mm²
0,5 to 1,5 mm²
6 mm
Slotted head 3mm 0,5 Nm
1309 0001 or 1309 0011
Fitting of auxiliary contacts:
Us
U
Use 20mm
se 20m
m
Use 35mm
screws for
sc
s
crews
r
screws for
1
1
1 module
modu
2 modules
Pozidriv PZ2 - 1 Nm