Troubleshooting
Problem
TSP power pack does not run at all.
Display shows CODE 08.
TSP power pack does not run at all.
Display shows CODE 10.
TSP power pack does not run at all.
Display shows CODE 12.
TSP power pack does not run at all.
Display shows CODE 15.
26
Cause
Incoming voltage too low for
TSP power pack operation.
Control board is over
heating.
Excessive current protection
enabled.
Motor not spinning (no
current to motor).
Solution
1.
Set TSP power pack to OFF and
disconnect power to TSP power
pack.
2.
Remove other equipment that uses
the same circuit.
3.
Locate a good voltage supply to
avoid damage to electronics.
1.
Make sure motor air intake is not
blocked.
2.
Make sure fan is securely attached
to motor shaft.
3.
Replace control board.
4.
Replace motor.
Cycle power on and off.
1.
Set TSP power pack to OFF and
disconnect power to TSP power
pack.
2.
Remove top half of shroud frame and
shroud.
3.
Set TSP power pack to OFF and spin
pump crank 1/2 turn. Restart TSP
power pack. If TSP power pack runs,
replace control board. If TSP power
pack does not run, continue to step 5.
4.
Turn power on. If code continues,
replace control board.