E5@C-T Controller Setup - Omron E5C-T Series Communications Manual

Digital temperature controllers programmable type
Table of Contents

Advertisement

7 Component Communications
7-1-3

E5@C-T Controller Setup

This section describes the settings necessary to start component communications and the set point
calculations that are used to perform target point calculations at the slaves.
To perform component communications, change the parameter settings in the communications setting
level to the values that are given below.
*
Parameter details are the same as for programless communications. Refer to 6-2 E5
Parameter
Protocol setting
Communications unit
number
Communications baud rate
Send data wait time
Highest communications
unit No.
Note: To use component communications, the input type and, if an analog input is used, the decimal point position
must be set to the same values for all of the E5@C-T/E5@C Controllers. The operation will not work correctly
if the position of the decimal point is different.
The parameters that are used for component communications are shown with a gray background in the
following diagram. All of these parameters are displayed if you set the Protocol Setting parameter to
cmp. (Some of the parameters are always displayed.)
Power ON
Operation Level
25
0
Press O Key
for at least 3 s.
Initial Setting Level
in-t
5
*
These parameters are displayed regardless of the setting of the Protocol Setting parameter.
Note: The Communications Data Length, Communications Stop Bits, and Communications Parity parameters in
the communications setting level are not displayed.
7 - 4
Master (E5@C-T)
CMP
0
57.6 (recommended)
1 (recommended)
Highest communications unit number of
all the slaves
Adjustment Level
Press O Key
for less than 1 s.
l.adj
Adjustment Level
Display
1234
M
at
AT Execute/Cancel
off
M
cmwt
Communications
on
Writing
*
M
Press O Key
for at least 1 s.
Communications Setting Level
Press O Key
for less than 1 s.
Protocol Setting
psel
cmp
M
u-no
Communications
0
Unit No.
M
bps
Communications
57.6
Baud Rate
M
sdwt
Send Data Wait
*
20
Time
M
Communications unit No. = 0 (master) Communications unit number ≠ 0
Highest
maxu
Communications
0
Unit No.
M
Receive Data
rwat
Wait Time
1000
M
E5C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
Set value
CMP
A number is set for each slave in order
from 1.
57.6 (recommended)
1 (recommended)
Setting is not necessary
(The parameter is not displayed.)
*
*
*
(slave (Fixed-value Controller)
sps
SP Slope
1.000
M
spos
SP Offset
0.0
M
@
C-T Controller Setup.