Current Transformer Ratings
Max. continuous heater current
Dielectric strength
Vibration resistance
Weight
Accessories (E54-CT3 only)

Controller Characteristics

Setting accuracy*
Indication accuracy
Hysteresis
Proportional band
Integral (reset) time
Derivative (rate) time
Alarm output setting range
Control period
Sampling period
Output refresh period
Display refresh period
Input shift range
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Memory protection
Enclosure ratings
Weight
*The accuracy of U thermocouples under temperatures from –150° to 400°C (–240° to 700°F) is ±2°C (±3.6°F) ±1 digit. Accuracy is reduced
below –150°C (–240°F). The accuracy of R and S thermocouples under 0° to 200°C (0° to 400°F) is ±3°C (±5.4°F) ±1 digit. The accuracy of the
B thermocouple below 400°C (750°F) is not guaranteed.
Output Unit Characteristics
Relay unit life expectancy
50 A
1,000 VAC (for 1 min)
50 Hz (approx. 10G)
E54-CT1: Approx. 11.5 g; E54-CT3: Approx. 50 g
Contact: 2; Plug: 2
(±0.3% of set value or ±1°C, whichever greater) ±1 digit max.
(±0.3% of indication value or ±1°C, whichever greater) ±1 digit max. (Set value coincides with
the indicated value, because no relative error exists between both values.)
0.0° to 999.9 °C/°F (in units of 0.1°C/°F) (during ON/OFF control action)
0.0° to 999.9 °C/°F (in units of 0.1°C/°F)
0 to 3,999 s (in units of 1 s)
0 to 3,999 s (in units of 1 s)
Thermocouple: –999° to 9,999°C/°F (in units of 1°C/°F)
Platinum resistance thermometer: –99.9° to 999.9°C/°F (in units of 0.1°C/°F)
Pulse output: 1 to 99 s (in units of 1 s)
500 ms
500 ms
500 ms
–99.9° to 999.9°C/°F (in units of 1°C/°F)
20 MΩ min. (at 500 VDC) (measured with a Control Output Unit attached)
2,000 VAC, 50/60 Hz for 1 minute between terminals of different polarities (measured with a
Control Output Unit attached)
Malfunction: 2 to 55 Hz, 2G 10 minutes each in X, Y, and Z directions
Destruction: 10 to 55 Hz, 0.75-mm double amplitude 2 hours each in X, Y, and Z directions
2
Malfunction: 200 m/s
3 times each in 6 directions
2
Destruction: 300 m/s
3 times each in 6 directions
Operating: –10° to 55°C (with no icing)
Storage:
–25° to 65°C (with no icing)
Operating: 35% to 85%
Non-volatile memory
Front panel: IEC standard IP50
Rear case:
IEC standard IP20
Terminals:
IEC standard IP00
Approx. 310 g; mounting bracket: approx. 50 g
Mechanical: 10,000,000 operations min.
Electrical:
100,000 operations min.
E5AX-BA/BAH/E5EX-BA/A02/A03