6 Programless Communications
Communications Setting Level
Display condition: The Protocol Setting parameter must be set to fins or mcp4
The Protocol Setting parameter must be set to cmp and the Communications Unit No. parameter must
be set to 0 (master).
Parameter name
Highest Communications Unit No.
6-2-5

Areas and First Address of Linked Data

Two areas are used in PLC memory by the E5@C-T, an upload area and a download area. The upload
area is used to monitor the process value, status, and other information from the E5@C-T. The down-
load area is used to write the fixed SP, segment SPs, segment times, alarm values, and other values to
the E5@C-T.
Address
XXXX Response Flag
Upload
Area
+24 Monitor Value 23
+25 Request Flag
+26 Operation
Downloa
+27 Set Value 1
d Area
+28 Set Value 2
+69 Set Value 43
The Response Flag, Communications Status, Request Flag, and Operation Command Code all have
special functions that cannot be changed. Refer to the following sections for application methods.
Request Flag: 6-3-1 Controlling Programless Communications with the Request Flag
Response Flag: 6-3-2 Response Flag
Operation Command Code: 6-3-4 Operation Command Codes
Communications Status: 6-3-5 Confirming Operation of Programless Communications
The portion of PLC memory to use is set with the Area, First Address Upper Word, and First Address
Lower Word parameters.
Note: If more than one E5
to the same value for all of them. The E5
words that start from the specified starting address, the E5
words that start from the specified starting address plus 70 words, and the E5
number 2 will use the words that start from the specified starting address plus 140 words
6 - 8
Displayed characters
maxu
Data in PLC
memory
This flag indicates the completion of processing for the Request Flag.
+1 Communications
The status that is given at this address is used in the PLC to check the operation
Status
of programless communications.
+2 Monitor Value 1
Information from the E5@C-T, such as the PV or status, is set at these addresses.
The parameters that are actually used are set in the upload settings.
+3 Monitor Value 2
· · ·
This flag is used to control programless communications.
The operation command that corresponds to the code is sent.
Command Code
The set values at these addresses are written to the E5@C-T, such as to the fixed
SP, segment SPs, segment times, and alarm values. The parameters that are
actually used are set in the download settings.
· · ·
@
C-T Controller is connected to the same communications line, set the starting address
E5C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
Setting range
0 to 99
@
C-T Controller with communications unit number 0 will use the
@
C-T Controller with unit number 1 will use the
Default
0
@
C-T Controller with unit