The variable type is converted to 2-byte ASCII and loaded to the frame. The following table shows the
available variable types.
Variable type
C0/80
C1/81
C3/83
C4/84
C5/85
C9/89
DA/9A
Note: Setup area 1 has no read-only parameters, so there is no variable type "C2."
The following table summarizes setup areas 0 and 1.
Area
Setup area 0
Setting area 1
The type code depends on the parameter. Refer to 3-1 Variable Area (Setting Range) List for details.
2-2-4

Addresses

An address is appended to each of the variable types. Express addresses in 2-byte hexadecimal and
append them for the specified access size. The address depends on the parameter. Refer to 3-1 Vari-
able Area (Setting Range) List for details.
2-2-5

Number of Elements

The number of elements is expressed in 2-byte hexadecimal. The range that can be specified for the
number of elements depends on the command. Refer to 2-3 Detailed Description of the Services for
details.
2-2-6

List of Services (Main Request Codes and Sub-Request Codes)

MRC
SRC
01
01
01
02
01
04
01
13
05
03
06
01
08
01
30
05
Note: No commands will be accepted and no responses will be returned when a memory error (RAM error) has
occurred or the Controller is initializing (until the Controller recognizes the process value after the power is
turned ON).
E5C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
2 CompoWay/F Communications Procedures
R/O (read only) parameter for setup area 0.
R/W parameter for setup area 0.
R/W parameter for setup area 1.
R/W parameters for setup area 0 (program setting level, currently selected number).
R/W parameter for setup area 0.
R/W parameter for setup area 1.
R/W parameters for setup area 0 (program setting level, all).
This area groups together the protect, manual control, operation, program setting,
adjustment, and PID setting levels.
This area groups together the initial setting, communications setting, advanced
function setting, and calibration levels.
Name of service
Read Variable Area
Write Variable Area
Composite Read from Variable Area This service reads from the variable area in the
Composite Write to Variable Area
Read Controller Attributes
Read Controller Status
Echoback Test
Operation Command
Description
Description
Processing
This service reads from the variable area.
This service writes to the variable area.
order specified by the parameters.
This service writes to the variable area in the order
specified by the parameters.
This service reads the model number and
communications buffer size.
This service reads the operating status.
This service performs an echoback test.
This service performs operations such as
RUN/RESET, executing/stopping AT (auto-tuning),
and moving to setup area 1.