5.3.1.2 Cold-Starting the UPSs Using Batteries

Step 1 Switch on the external battery circuit breaker (if any).
Step 2 Press ON/MUTE to start the UPSs. The UPSs will enter the standby mode. Press
and hold SELECT for 1s on a non-setting screen to access the login screen for
parameter settings. The initial password is 000001. Enter the correct password to
access the UPS setting mode.
Step 3 Set the output voltage based on site requirements.
Output Voltage
Step 4 Operate the UPSs one by one to set the number of parallel output UPSs. Press
SELECT, go to the setting screen, and set parallel system parameters. Press ON/
MUTE+SELECT to return to the standby screen.
Issue 01 (2020-10-26)
Copyright © Huawei Technologies Co., Ltd.
Description
● Default value: 1
● Value range: 1–2
Description
You need to shut down the inverter
before changing the output voltage.
220: indicates that the output voltage
is 220 V AC.
230: indicates that the output voltage
is 230 V AC (default value).
240: indicates that the output voltage
is 240 V AC.