ENGLISH
IONISATION CURRENT
To measure the ionisation current, remove the jumper between
terminals 30-31 on the printed circuit with the burner off.Connect
to the terminals a microammeter having a suitable scale to have
the burner restart. Once the flame has appeared it will be possible
to measure the ionisation current, the minimum value of which to
ensure the working of the equipment is shown in the specific wiring
diagram. At the end of the measurement, connect the jumper that
has been disconnected.
DIAGRAM FOR REGULATING THE ELECTRODE DISK DISTANCE
1 - Ionisation electrode
2 - Ignition electrode
3 - Flame disc
4 - Mixer
5 - Gas delivery pipe
E - WARNING: nozzle hole outlet near the electrode tip.