Choice Of Measuring Site; Direction Of Flow; Full Pipes; Installation In Horizontal Pipes - Siemens SITRANS F US SONOFLO Handbook

Ultrasonic flowmeter type sonokit 1-track dn 100 - dn 4000
Hide thumbs Also See for SITRANS F US SONOFLO:
Table of Contents

Advertisement

® ® ® ® ®
SITRANS F US SONOFLO

Direction of flow

Full pipes

Installation in horizontal
pipes
4

2. Choice of measuring site

Double arrow marked with "+" and "−" on the sensor.
+ indicates direction of flow when the electrical connections correspond to the ones described in
the manual.
SFIDK.PS.029.V3.02 - 521H0553
The sensor must always be completely filled
with liquid.
The following installations should be avoided:
Installation at the highest point of the pipe
system
Installation in vertical pipes with free outlet
With partially full pipes or pipes with free outlet
the flowmeter should be located in a U-shaped
tube.
Installing the transducers in horizontal position
is recommended.