Panasonic Aquarea B1 Planning And Installation Manual page 62

Air-to-water heat pumps split systems and compact systems
Table of Contents

Advertisement

Planning
Aquarea T-CAP, combination hydro-module, single- phase, Heating and cooling (ADC), Generation H
WH-ADC1216H6E5 / WH-UX09HE5
t
(°C)
30
35
V
t
(°C)
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
a
Hzg
zu
Hzg
zu
Hzg
zu
25
13.60
1.50
9.07
13.60
1.71
7.95
13.20
1.93
7
9.00
1.64
5.49
9.00
1.86
4.84
9.00
2.16
2
9.00
2.36
3.81
9.00
2.51
3.59
9.00
2.78
-7
9.00
2.71
3.32
9.00
3.16
2.85
9.00
3.62
-15
9.00
3.24
2.78
9.00
3.51
2.56
9.00
3.91
WH-ADC1216H6E5 / WH-UX12HE5
t
(°C)
30
35
V
t
(°C)
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
a
Hzg
zu
Hzg
zu
Hzg
zu
25
13.60
1.55
8.77
13.60
1.76
7.73
13.40
2.10
7
12.00
2.18
5.50
12.00
2.53
4.74
12.00
2.96
2
12.00
3.19
3.76
12.00
3.49
3.44
12.00
3.87
-7
12.00
3.85
3.12
12.00
4.41
2.72
12.00
4.98
-15
12.00
4.75
2.53
12.00
4.96
2.42
12.00
5.17
Aquarea T-CAP, combination hydro-module, Three-phase, Heating and cooling (ADC), Generation H
WH-ADC0916H9E8 / WH-UX09HE8 or WH-ADC0916H9E8 / WH-UQ09HE8
t
(°C)
30
35
V
t
(°C)
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
a
Hzg
zu
Hzg
zu
Hzg
zu
25
13.60
1.50
9.07
13.60
1.71
7.95
13.20
1.93
7
9.00
1.64
5.49
9.00
1.86
4.84
9.00
2.16
2
9.00
2.36
3.81
9.00
2.51
3.59
9.00
2.78
-7
9.00
2.71
3.32
9.00
3.16
2.85
9.00
3.62
-15
9.00
3.24
2.78
9.00
3.51
2.56
9.00
3.91
WH-ADC0916H9E8 / WH-UX12HE8 or WH-ADC0916H9E8 / WH-UQ12HE8
t
(°C)
30
35
V
t
(°C)
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
a
Hzg
zu
Hzg
zu
Hzg
zu
25
13.60
1.55
8.77
13.60
1.76
7.73
13.40
2.10
7
12.00
2.18
5.50
12.00
2.53
4.74
12.00
2.96
2
12.00
3.19
3.76
12.00
3.49
3.44
12.00
3.87
-7
12.00
3.85
3.12
12.00
4.41
2.72
12.00
4.98
-15
12.00
4.75
2.53
12.00
4.96
2.42
12.00
5.41
WH-ADC0916H9E8 / WH-UX16HE8 or WH-ADC0916H9E8 / WH-UQ16HE8
t
(°C)
30
35
V
t
(°C)
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
a
Hzg
zu
Hzg
zu
Hzg
zu
25
16.00
2.02
7.92
16.00
2.58
6.20
16.00
2.90
7
16.00
3.35
4.77
16.00
3.74
4.28
16.00
4.30
2
16.00
4.67
3.43
16.00
5.21
3.10
16.00
5.74
-7
16.00
5.85
2.74
16.00
6.42
2.49
16.00
7.00
-15
16.00
6.30
2.54
16.00
6.89
2.32
16.00
7.50
Performances of split systems with combination hydro-module in cooling mode
Aquarea LT, combination hydro-module, single- phase, heating and cooling (ADC), Generation H
WH-ADC0309H3E5(B) / WH-UD03HE5-1
t
(°C)
7
14
V
t
(°C)
P
(kW) P
(kW)
EER
P
(kW) P
(kW)
EER
P
(kW) P
a
Klg
zu
Klg
zu
Klg
zu
43
2.90
1.20
2.42
3.50
1.20
2.92
3.00
0.88
35
3.20
1.04
3.08
3.90
1.07
3.64
3.30
0.74
25
3.20
0.73
4.38
4.10
0.86
4.77
3.50
0.59
18
2.40
0.42
5.71
4.40
0.73
6.03
3.70
0.49
WH-ADC0309H3E5(B) / WH-UD07HE5-1
t
(°C)
7
14
V
t
(°C)
P
(kW) P
(kW)
EER
P
(kW) P
(kW)
EER
P
(kW) P
a
Klg
zu
Klg
zu
Klg
zu
43
4.85
2.65
1.83
6.00
2.82
2.13
4.80
1.98
35
6.00
2.28
2.63
6.60
2.48
2.66
6.00
1.68
25
7.00
1.90
3.68
8.47
1.78
4.76
6.00
1.27
16
4.80
0.80
6.0
7.20
1.16
6.21
6.00
1.13
WH-ADC1216H6E5 / WH-UD12HE5
t
(°C)
7
14
V
t
(°C)
P
(kW) P
(kW)
EER
P
(kW) P
(kW)
EER
P
(kW) P
a
Klg
zu
Klg
zu
Klg
zu
43
7.80
3.80
2.05
11.10
3.19
3.48
8.00
2.85
35
10.00
2.56
3.91
12.00
2.67
4.49
10.00
2.40
25
12.08
2.90
4.17
15.70
2.05
7.66
10.00
1.97
16
7.86
1.18
6.66
13.15
1.40
9.39
10.00
1.73
118
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
40
45
50
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
Hzg
zu
Hzg
zu
Hzg
6.84
12.80
2.14
5.98
12.00
2.41
4.98
11.20
4.17
9.00
2.46
3.66
9.00
2.76
3.26
9.00
3.24
9.00
3.05
2.95
9.00
3.56
2.53
9.00
2.49
9.00
4.07
2.21
9.00
4.27
2.11
9.00
2.30
9.00
4.30
2.09
9.00
4.73
1.90
9.00
40
45
50
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
Hzg
zu
Hzg
zu
Hzg
6.38
13.20
2.43
5.43
12.60
2.66
4.74
12.00
4.05
12.00
3.39
3.54
12.00
3.78
3.17
12.00
3.10
12.00
4.25
2.82
12.00
4.86
2.47
12.00
2.41
12.00
5.54
2.17
12.00
5.90
2.03
12.00
2.22
11.00
5.38
2.04
10.80
5.82
1.86
10.50
40
45
50
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
Hzg
zu
Hzg
zu
Hzg
6.84
12.80
2.14
5.98
12.00
2.41
4.98
11.20
4.17
9.00
2.46
3.66
9.00
2.76
3.26
9.00
3.24
9.00
3.05
2.95
9.00
3.56
2.53
9.00
2.49
9.00
4.07
2.21
9.00
4.27
2.11
9.00
2.30
9.00
4.30
2.09
9.00
4.73
1.90
9.00
40
45
50
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
Hzg
zu
Hzg
zu
Hzg
6.38
13.20
2.43
5.43
12.60
2.66
4.74
12.00
4.05
12.00
3.39
3.54
12.00
3.78
3.17
12.00
3.10
12.00
4.25
2.82
12.00
4.86
2.47
12.00
2.41
12.00
5.54
2.17
12.00
5.90
2.03
12.00
2.22
12.00
5.86
2.05
11.80
6.24
1.89
11.10
40
45
50
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
Hzg
zu
Hzg
zu
Hzg
5.52
16.00
3.36
4.76
16.00
3.74
4.27
16.00
3.75
16.00
4.80
3.33
16.00
5.43
2.95
16.00
2.79
16.00
6.31
2.54
16.00
6.99
2.31
16.00
2.29
16.00
7.57
2.11
16.00
8.10
1.97
16.00
2.13
16.00
8.10
1.98
16.00
8.48
1.89
15.20
WH-ADC0309H3E5(B) / WH-UD05HE5-1
18
7
14
(kW)
EER
P
(kW) P
(kW)
EER
P
(kW) P
(kW)
EER
P
(kW) P
Klg
zu
Klg
zu
Klg
3.41
3.30
1.53
2.16
4.10
1.52
2.70
4.40
4.46
4.50
1.67
2.69
5.50
1.68
3.27
5.00
5.93
5.00
1.43
3.50
6.30
1.50
4.20
5.40
7.55
4.50
0.89
5.06
5.00
0.90
5.56
5.70
WH-ADC0309H3E5(B) / WH-UD09HE5-1
18
7
14
(kW)
EER
P
(kW) P
(kW)
EER
P
(kW) P
(kW)
EER
P
(kW) P
Klg
zu
Klg
zu
Klg
2.42
5.20
2.85
1.83
6.99
3.84
1.82
5.60
3.57
7.99
2.88
2.77
7.60
3.20
2.38
7.00
4.72
7.85
2.40
3.27
10.20
2.46
4.15
7.00
5.31
5.40
1.00
5.40
8.40
1.62
5.19
7.00
WH-ADC1216H6E5 / WH-UD16HE5
18
7
14
(kW)
EER
P
(kW) P
(kW)
EER
P
(kW) P
(kW)
EER
P
(kW) P
Klg
zu
Klg
zu
Klg
2.81
7.75
3.40
2.28
13.80
5.95
2.32
9.70
4.17
12.20
4.76
2.56
15.00
4.98
3.01
12.20
5.07
14.40
3.92
3.67
19.20
3.83
5.01
12.20
5.78
9.20
1.62
5.68
16.40
2.58
6.36
12.20
Aquarea LT, Combination hydro-module, Three-phase, Heating and cooling (ADC), Generation H
WH-ADC0916H9E8 / WH-UD09HE8
55
t
(°C)
7
V
(kW)
COP
t
(°C)
P
(kW) P
(kW)
zu
a
Klg
zu
2.67
4.19
43
5.52
2.54
3.06
2.94
35
7.00
2.23
4.07
2.21
25
8.35
1.77
4.46
2.02
16
7.50
1.15
5.16
1.74
WH-ADC0916H9E8 / WH-UD16HE8
t
(°C)
7
V
55
t
(°C)
P
(kW) P
(kW)
a
Klg
zu
(kW)
COP
43
7.75
3.40
zu
2.89
4.15
35
12.20
4.76
4.16
2.88
25
14.40
3.92
5.47
2.19
16
9.20
1.62
6.26
1.92
6.26
1.68
Aquarea T-CAP, combination hydro-module, single- phase, Heating and cooling (ADC), Generation H
WH-ADC1216H6E5 / WH-UX09HE5
t
(°C)
7
V
t
(°C)
P
(kW) P
(kW)
a
Klg
zu
55
43
7.80
3.80
(kW)
COP
35
10.00
2.56
zu
2.67
4.19
25
12.08
2.90
3.06
2.94
16
7.86
1.18
4.07
2.21
4.46
2.02
5.16
1.74
Aquarea T-CAP, combination hydro-module, Three-phase, Heating and cooling (ADC), Generation H
WH-ADC0916H9E8 / WH-UX09HE8
t
(°C)
7
V
55
t
(°C)
P
(kW) P
(kW)
a
Klg
zu
(kW)
COP
zu
43
6.25
2.66
2.89
4.15
35
7.00
2.21
4.16
2.88
25
7.65
1.91
5.47
2.19
18
7.00
1.36
6.26
1.92
6.62
1.68
WH-ADC0916H9E8 / WH-UX16HE8
t
(°C)
7
V
t
(°C)
P
(kW) P
(kW)
a
Klg
zu
55
43
7.10
3.31
(kW)
COP
zu
35
12.20
4.76
4.00
4.00
25
14.00
4.00
5.91
2.71
18
8.50
1.70
7.50
2.13
8.62
1.86
8.96
1.70
Performances of split systems with hydro-module in heating mode
Aquarea LT, Split, single- phase, Heating and Cooling (SDC), Generation H
WH-SDC03H3E5-1 / WH-UD03HE5-1
t
(°C)
30
V
t
(°C)
P
(kW) P
(kW)
a
Hzg
zu
25
3.20
0.42
18
7
3.20
0.58
(kW)
EER
zu
2
3.20
0.82
1.53
2.88
-7
3.20
1.08
1.33
3.76
-15
3.20
1.26
1.06
5.09
0.90
6.33
WH-SDC05H3E5-1 / WH-UD05HE5-1
t
(°C)
30
V
t
(°C)
P
(kW) P
(kW)
a
Hzg
zu
18
25
5.00
0.74
(kW)
EER
zu
7
5.00
0.97
2.55
2.20
2
4.20
1.22
2.15
3.26
-7
4.20
1.46
1.77
3.96
-15
4.20
1.75
1.61
4.25
18
(kW)
EER
zu
4.00
2.43
2.96
4.12
2.79
4.37
2.45
4.98
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
WH-ADC0916H9E8 / WH-UD12HE8
14
18
EER
P
(kW) P
(kW)
EER
P
(kW) P
(kW)
EER
P
(kW) P
Klg
zu
Klg
zu
Klg
zu
2.17
7.69
2.77
2.78
5.60
1.80
3.11
7.80
3.80
3.14
8.30
2.32
3.58
7.00
1.52
4.61
10.00
2.56
4.72
10.90
1.78
6.12
7.00
1.24
5.65
12.08
2.90
6.52
9.10
1.20
7.58
8.00
1.13
7.08
7.86
1.18
14
18
EER
P
(kW) P
(kW)
EER
P
(kW) P
(kW)
EER
Klg
zu
Klg
zu
2.28
13.80
5.95
2.32
9.70
4.00
2.43
2.56
15.00
4.98
3.01
12.10
2.96
4.09
3.67
19.20
3.83
5.01
12.20
2.79
4.37
5.68
16.40
2.58
6.36
12.20
2.45
4.98
WH-ADC1216H6E5 / WH-UX12HE5
14
18
EER
P
(kW) P
(kW)
EER
P
(kW) P
(kW)
EER
P
(kW) P
Klg
zu
Klg
zu
Klg
zu
2.05
11.10
3.19
3.48
8.00
2.85
2.81
7.75
3.40
3.91
12.00
2.67
4.49
10.00
2.40
4.17
12.20
4.76
4.17
15.70
2.05
7.66
10.00
1.97
5.07
14.40
3.92
6.66
13.15
1.40
9.39
10.00
1.73
5.78
9.20
1.62
WH-ADC0916H9E8 / WH-UX12HE8
14
18
EER
P
(kW) P
(kW)
EER
P
(kW) P
(kW)
EER
P
(kW) P
Klg
zu
Klg
zu
Klg
zu
2.35
8.00
3.01
3.17
10.00
3.56
4.01
8.90
2.16
5.15
7.50
1.41
14
18
EER
P
(kW) P
(kW)
EER
P
(kW) P
(kW)
EER
Klg
zu
Klg
zu
2.15
9.80
3.31
2.96
2.56
12.20
3.50
3.49
3.50
14.00
2.94
4.76
5.00
10.00
1.70
5.88
35
40
COP
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
Hzg
zu
Hzg
zu
Hzg
zu
7.62
3.20
0.46
6.96
3.20
0.55
5.82
3.20
0.63
5.52
3.12
0.64
4.88
3.20
0.77
4.16
3.20
0.89
3.90
3.29
0.90
3.66
3.20
1.03
3.11
3.20
1.16
2.96
3.58
1.19
3.00
3.20
1.34
2.39
3.20
1.48
2.54
3.13
1.39
2.25
3.10
1.52
2.04
3.00
1.64
35
40
COP
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
Hzg
zu
Hzg
zu
Hzg
zu
6.76
5.00
0.82
6.10
5.00
1.02
4.90
5.00
1.22
5.15
5.00
1.08
4.63
5.00
1.28
3.91
5.00
1.48
3.44
4.20
1.35
3.11
4.20
1.50
2.80
4.20
1.65
2.88
4.20
1.62
2.59
4.00
1.72
2.33
3.80
1.82
2.40
4.20
1.94
2.17
3.80
1.96
1.94
3.40
1.98
Planning
7
14
18
(kW)
EER
P
(kW) P
(kW)
EER
P
(kW) P
(kW)
EER
Klg
zu
Klg
zu
2.05
11.10
3.19
3.48
8.00
2.85
2.81
3.91
12.00
2.67
4.49
10.00
2.40
4.17
4.17
15.70
2.05
7.66
10.00
1.97
5.08
6.66
13.15
1.40
9.39
10.00
1.73
5.78
7
14
18
(kW)
EER
P
(kW) P
(kW)
EER
P
(kW) P
(kW)
EER
Klg
zu
Klg
zu
2.28
13.80
5.95
2.32
9.70
4.00
2.43
2.56
15.00
4.98
3.01
12.20
2.96
4.12
3.67
19.20
3.83
5.01
12.20
2.79
4.37
5.68
16.40
2.58
6.36
12.20
2.45
4.98
7
14
18
(kW)
EER
P
(kW) P
(kW)
EER
P
(kW) P
(kW)
EER
Klg
zu
Klg
zu
2.66
2.81
4.12
5.32
45
50
55
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
Hzg
zu
Hzg
zu
5.08
3.20
0.73
4.38
3.20
0.82
3.90
3.60
3.20
1.05
3.05
3.20
1.20
2.67
2.76
3.20
1.33
2.41
3.20
1.49
2.15
2.16
3.20
1.67
1.92
3.20
1.86
1.72
1.83
2.80
1.78
1.57
2.75
1.92
1.43
45
50
55
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
Hzg
zu
Hzg
zu
4.10
5.00
1.35
3.70
5.00
1.49
3.36
3.38
5.00
1.68
2.98
5.00
1.89
2.65
2.55
4.15
1.86
2.23
4.10
2.07
1.98
2.09
3.70
1.95
1.90
3.55
2.08
1.71
1.72
3.20
2.05
1.56
3.00
2.12
1.42
119