Product Description
Compact system / HT series / G Generation
HT series
Single-phase (230 V / 50 Hz), Heating and Cooling
Compact device
WH-MHF09G3E5
Model
B9
Heating capacity at +7 °C (A7/W35)
kW
9.00
COP at +7 °C (A7/W35)
4.64
Heating capacity at +2 °C (A2/W35)
kW
9.00
COP at +2 °C (A2/W35)
3.45
Heating capacity at -7 °C (A–7/W35)
kW
9.00
COP at -7 °C (A–7/W35)
2.74
Heating capacity at +7 °C (A7/W65)
kW
9.00
COP at +7 °C (A7/W65)
2.27
Heating capacity at +2 °C (A2/W65)
kW
9.00
COP at +2 °C (A2/W65)
1.89
Heating capacity at -7 °C (A–7/W65)
kW
8.90
COP at -7 °C (A–7/W65)
1.63
Energy efficiency class
at 35 / 55 °C
1
i / i
Sound pressure level
dB(A)
51
Sound power (A7/W55)
dB(A)
68
Dimensions
H x L x W
mm
1,410 x 1,283 x 320
Weight
kg
151
Water-side connection
mm
28
High efficiency pump
Rotation speed stages
7
Power consumption (min./ max.) W
Water flow rate (A7/W35)
l/min
25.8
Power of E-heating element
kW
3
Power consumption
kW
1.94
Operating and start up current
A
9.3
Max. power consumption on network connection 1 / 2
A
28.5 / 13.0
Recommended fuse for network connection 1 / 2
A
30 / 30
Recommended cable cross section for network connection 1 / 2 mm²
3 x 4.0 or 6.0 / 3 x 4.0
Pre-filled refrigerant (R410A) / CO
-equivalent
kg / t CO
-Equ. 1.92 / 3.406
2
2
Operating range
Outside temperature (H / K)
°C
-20 to 35 / 16 to 43
Water outlet temperature (H / K) °C
25 to 60 / 5 to 20
The COP details relate to 230 V in conformance with the EC Directives 2003/32/EC. Power details in conformance with EN 14511.
The information about the energy efficiency classes is based on the official ErP specifications (EU Ordinance No. 811/2013, EN 14511 and EN 14825) for heat pumps, which have been
in force since 26. September 2015. The efficiency classes marked with an asterisk (*) correspond to the new A+++ class to be introduced starting in September 2019. Other ErP relevant
information is included in the respective product data sheets.
1 Energy efficiency class scale from A++ to G.
4.7
Control
4.7.1 Operating unit
The Aquarea heat pumps can be operated and programmed through the operating unit included
in the scope of delivery. The operating unit has a display for the important operating parame-
ters and various operating keys for retrieving, setting, activating and deactivating the control
functions.
To combine the Aquarea heat pumps with external devices such as a solar system or a room
thermostat, the operating unit is equipped with the requisite interfaces. The corresponding func-
tions are only available if the accessories in question are connected and activated
ternal interfaces (in-/outputs), p.
59,
optional on-site accessories, p.
180).
In the case of split systems, the operating unit is integrated into the hydro-module or combina-
tion hydro-module, but can be removed from the device to another room for separate instal-
lation. In the case of compact systems, the operating unit is always installed separately in the
building. The method for installing the operating unit is identical in both cases
bling and connecting the operating unit, p.
Depending on the device generation (F, G, H...), the heat pumps are equipped with various
operating units that provide different functions.
52
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Three-phase (400 V / 50 Hz), heating
WH-MHF12G6E5
WH-MHF09G3E8
WH-MHF12G9E8
B9
B9
B9
12.00
9.00
12.00
4.46
4.64
4.46
12.00
9.00
12.00
3.26
3.45
3.26
12.00
9.00
12.00
2.52
2.14
2.52
12.00
9.00
12.00
2.22
2.29
2.22
10.30
9.00
10.30
1.84
1.89
1.84
9.60
8.90
9.60
1.62
1.63
1.62
i / i
i * / i
i * / i
52
51
52
69
68
69
1,410 x 1,283 x 320
1,410 x 1,283 x 320
1,410 x 1,283 x 320
151
162
162
28
28
28
7
7
7
34.4
25.8
34.4
6
3
9
2.69
1.94
2.69
12.8
3.0
4.1
29.0 / 26.0
14.5 / 13.0
10.8 / 13.0
30 / 30
16 / 16
16 / 16
3 x 4.0 or 6.0 / 3 x 4.0
5 x 1.5 / 3 x 1.5
5 x 1.5 / 5 x 1.5
1.92 / 3.406
-20 to 35 / 16 to 43
-20 to 35 / 16 to 43
-20 to 35 / 16 to 43
25 to 60 / 5 to 20
25 to 60 / 5 to 20
25 to 60 / 5 to 20
(→ 4.7.2 Ex-
→ 4.6.3.3 Accessories, p.
50,
→ 6.8.2 Connecting the
(→ 6.8.3 Assem-
186).
4.7.1.1 Operating unit for F- and G-Generation models
The operating unit is in the scope of delivery of the following models:
Split systems
WH-SHF09F3E5 + WH-UH09FE5
WH-SHF12F6E5 + WH-UH12FE5
WH-SHF09F3E8 + WH-UH09FE8
WH-SHF12F9E8 + WH-UH12FE8
i
Note
An overview of the structure and functions of the operating unit for the models of the F and G
generations is given in the planning handbook for split systems or compact systems from 2014.
Detailed information about the regulation functions is also given in the operating instructions and
in the service manual of the device in question.
4.7.1.2 Operating unit for H-Generation models
The operating unit is in the scope of delivery of the following models:
Split systems with combination
hydro-module
WH-ADC0309H3E5(B) + WH-UD03HE5-1
WH-ADC0309H3E5(B) + WH-UD05HE5-1
WH-ADC0309H3E5(B) + WH-UD07HE5-1
WH-ADC0309H3E5(B) + WH-UD09HE5-1
WH-ADC1216H6E5 + WH-UD12HE5
WH-ADC1216H6E5 + WH-UD16HE5
WH-ADC0916H9E8 + WH-UD09HE8
WH-ADC0916H9E8 + WH-UD12HE8
WH-ADC0916H9E8 + WH-UD16HE8
WH-ADC1216H6E5 + WH-UX09HE5
WH-ADC1216H6E5 + WH-UX12HE5
WH-ADC0916H9E8 + WH-UX09HE8
WH-ADC0916H9E8 + WH-UX12HE8
WH-ADC0916H9E8 + WH-UX16HE8
WH-ADC0916H9E8 + WH-UQ09HE8
WH-ADC0916H9E8 + WH-UQ12HE8
WH-ADC0916H9E8 + WH-UQ16HE8
!
IMPORTANT
The same operating unit is used for all models of the H-generation, but not all functions of the
operating unit are directly available for all models. For example, the domestic hot water mode
is directly available in the split systems with combination hydro-module and internal domestic
hot water tank, while this function is only available in split systems with standard hydro-module
and external domestic hot water tank after the external domestic water temperature sensor is
installed, electrically connected and enabled via the operating unit.
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Product Description
Compact systems
WH-MHF09G3E5'
WH-MHF12G6E5
WH-MHF09G3E8
WH-MHF12G9E8
Split systems with hydro-module
Compact systems
WH-SDC03H3E5-1 + WH-UD03HE5-1
WH-MDC05H3E5
WH-SDC05H3E5-1 + WH-UD05HE5-1
WH-MDC07H3E5
WH-SDC07H3E5-1 + WH-UD07HE5-1
WH-MDC09H3E5
WH-SDC09H3E5-1 + WH-UD09HE5-1
WH-MXC09H3E5
WH-SDC12H6E5 + WH-UD12HE5
WH-MXC12H6E5
WH-SDC16H6E5 + WH-UD16HE5
WH-MXC09H3E8
WH-SDC09H3E8 + WH-UD09HE8
WH-MXC12H9E8
WH-SDC12H9E8 + WH-UD12HE8
WH-MXC16H9E8
WH-SDC16H9E8 + WH-UD16HE8
WH-SXC09H3E5 + WH-UX09HE5
WH-SXC12H6E5 + WH-UX12HE5
WH-SXC09H3E8 + WH-UX09HE8
WH-SXC12H9E8 + WH-UX12HE8
WH-SXC16H9E8 + WH-UX16HE8
WH-SQC09H3E8 + WH-UQ09HE8
WH-SQC12H9E8 + WH-UQ12HE8
WH-SQC16H9E8 + WH-UQ16HE8
53

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents