Planning
5.2.2.5 Assembly conditions for hydro-modules and combination hydro-modules
The assembly conditions for the hydro-module or combination hydro-module are as follows:
● The hydro-module is only developed for indoor installation and may not be installed
outdoors.
● The installation space must be dry and frost-free and the installation location easily
accessible for maintenance work.
● Cables, pipelines and wall bushings should be arranged functionally and using the
shortest path (electrical cables, coolant and heating water pipelines).
● Ensure good air circulation in the installation room.
● There must not be any heat or vapour sources near the hydro-module. Even
laundries or other rooms with high humidity are not suitable, because high humidity
causes rusting and can damage the device.
● The condensation from the condensation drain of the hydro-module should be able
to run without obstacles, because incorrect draining can cause damage.
● Development of noise in the room should be taken into account
tics, p.
87).
● Do not mount the device near the door.
● Maintain the minimum distances
and combination hydro-modules, p.
● The hydro-module must be installed vertically on the wall, where the wall should be
strong and solid, so that no vibration occurs.
● In case electrical devices are installed on wooden buildings with metal strips or ca-
ble cleats, no electrical contacts are allowed between device and building accord-
ing to the corresponding standards for electrical work.
94
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
(→ 5.2.1 Acous-
(→ 5.2.2.6 Minimum distances for hydro-modules
95).
5.2.2.6 Minimum distances for hydro-modules and combination hydro-modules
Combination Hydro-module H-Generation
1
2
2
3
2
Hydro-module F-Generation
1
1
1
2
Minimum distances hydro-module F-Generation
1 Minimum distance: 300 mm
2 Minimum distance: 600 mm
!
IMPORTANT
As the compressor is in the outdoor unit of the split system, only the operation of the circulation
pump in the hydro-module or combination hydro-module needs to be taken into consideration as
the cause for the development of operating noises.
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Planning
Minimum distances combination hydro-module
H-Generation
1 Minimum distance: 300 mm
2 Minimum distance: 100 mm
3 Minimum distance: 700 mm
Hydro-module H-Generation
1
1
1
2
Minimum distances hydro-module H Generation
1 Minimum distance: 100 mm
2 Minimum distance: 800 mm
95