Planning
5.2.3.2 Minimum distances for compact device
Minimum distance of the compact device to the neighbouring walls and objects, showing
air flow direction
1
3
Correct arrangement of multiple compact devices with representation of the air flow
direction
Wrong
98
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
2
1 Minimum distance: 100 mm
2 Minimum distance: 300 mm
3 Minimum distance: 1,000 mm
2
Correct
1 Minimum distance: 100 mm
1
5.2.3.3 Securing the compact device
The compact device must be mounted on a flat, horizontal and solid surface. Take the weight of
980
the water into consideration, too, besides the weight of the device. You need four M12 anchor
775
bolts, with a tensile force of more than 15,000 N.
Minimum requirements for anchoring the compact device on the floor over a foundation
(A and B) or directly in the floor plate (C)
A
4
2
4
1
×100
3
≥ 60
1
A Front view: Anchoring by means of foundation
1 Flooring
2 Gravel filling
3 Strip foundation
4 Anchor bolts
5 Drain pipes
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Planning
B
980
775
C
60 mm
3
4
300 mm
200
3
5
4
×100
2
All dimensions in mm
≥ 60
200
B Plan view
1
C Detailed view Anchoring in the floor plate
3
5
2
99