Panasonic Aquarea B1 Planning And Installation Manual page 60

Air-to-water heat pumps split systems and compact systems
Table of Contents

Advertisement

Planning
Models
Mains connection 1
Phases
Max. current
consumption (A)
WH-MXC12H9E8
3
11.9
WH-MXC16H9E8
3
15.5
WH-MHF12G9E8
3
10.8
FI protection switch and mains connections
FI protection
switch
Mains connections
L
A1
L
A1
Mains connection 1
Connection conditions
For compact devices of the H generation
● For the connection to the electricity supply, use an approved power cord with poly-
chloroprene material, symbol 60245 IEC 57 or higher, for mains connection.
For the compact device WH-MDC05H3E5:
● Mains supply 1 of this device fulfils EN/ IEC 61000-3-2.
● Mains supply 1 of this device fulfils EN/ IEC 61000-3-3 and can be connected to
the current supply grid.
● Mains supply 2 of this device fulfils EN/ IEC 61000-3-2.
● The main supply 2 of this device fulfills IEC/EN 61000-3-11 and is to be connected
to a suitable voltage source, whose maximum allowed system impedance at the
interface is Z
= 0.257 Ω. Connect to the EVU to ensure that the mains supply 2
max
is only connected to a grid with the maximum of this impedance.
For the compact devices WH-MDC07H3E5 and WH-MDC09H3E5:
● Mains supply 1 of this device fulfils EN/IEC 61000-3-12, provided that the short-cir-
cuit power S
at the transfer point of the energy provider to the operator is great-
k
er than or equal to 750 kW. The installer or operator of the device is, therefore,
responsible for ensuring, in case a consultation with the EVU is needed, that the
device is only connected, if the short-circuit power S
750 kW.
● Mains supply 1 of the device fulfils ICE/ EN 61000-3-11 and is to be connected to
a suitable voltage source, which has a current rating ≥100 A per phase. Connect
to the EVU to ensure that the current rating at the transfer point is sufficient for the
device.
● Mains supply 2 of this device fulfils EN/ IEC 61000-3-2.
● The main supply 2 of this device fulfills IEC/EN 61000-3-11 and is to be connected
to a suitable voltage source, whose maximum allowed system impedance at the
interface is Z
= 0.257 Ω. Connect to the EVU to ensure that the mains supply 2
max
is only connected to a grid with the maximum of this impedance.
114
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
L
L
L
N
L
L
A1
A2
A3
C1
C2
L
L
L
N
L
L
A1
A2
A3
C1
C2
Mains connection 2
Max. power
Phases
Max. current
consumption (kW)
consumption (A)
consumption (kW)
7.91
3
13.0
10.27
1
13.0
7.07
3
13.0
Terminals on compact device
L
L
N
L
L
L
N
1
A2
A3
C1
C2
C3
Terminals on disconnector of the mains connection
L
L
N
L
L
L
N
2
A2
A3
C1
C2
C3
Mains connection 2
is greater than or equal to
k
L
N
C3
L
N
C3
For the compact devices WH-MXC09H3E5 and WH-MXC12H6E5:
Max. power
9.0
9.0
9.0
For the compact devices WH-MXC09H3E8, WH-MXC16H9E8 and WH-MHF09G3E8:
For the compact devices WH-MXC12H9E8 and WH-MHF12G9E8:
For the compact devices WH-MHF09G3E5 and WH-MHF12G6E5:
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
● Mains supply 1 of this device fulfils EN/IEC 61000-3-12, provided that the short-cir-
cuit power S
at the transfer point of the energy provider to the operator is greater
k
than or equal to 1700 kW. The installer or operator of the device is, therefore,
responsible for ensuring, in case a consultation with the EVU is needed, that the
device is only connected, if the short-circuit power S
1700 kW.
● Mains supply 1 of the device fulfils ICE/ EN 61000-3-11 and is to be connected to
a suitable voltage source, which has a current rating ≥100 A per phase. Connect
to the EVU to ensure that the current rating at the transfer point is sufficient for the
device.
● Mains supply 2 of this device fulfils EN/ IEC 61000-3-12.
● The main supply 2 of this device fulfills IEC/EN 61000-3-11 and is to be connected
to a suitable voltage source, whose maximum allowed system impedance at the
interface is Z
= 0.453 Ω. Connect to the EVU to ensure that the mains supply 2
max
is only connected to a grid with the maximum of this impedance.
● Mains supply 1 and mains supply 2 of this device fulfils EN/ IEC 61000-3-2.
● Mains supply 1 and mains supply 2 of this device fulfils EN/ IEC 61000-3-3 and can
be connected to the current supply grid.
● Mains supply 1 of this device fulfils EN/ IEC 61000-3-2.
● Mains supply 1 of this device fulfils EN/ IEC 61000-3-3 and can be connected to
the current supply grid.
● Mains supply 2 of this device fulfils EN/ IEC 61000-3-2.
● The main supply 2 of this device fulfills IEC/EN 61000-3-11 and is to be connected
to a suitable voltage source, whose maximum allowed system impedance at the
interface is Z
= 0.449 Ω. Connect to the EVU to ensure that the mains supply 2
max
is only connected to a grid with the maximum of this impedance.
● Mains supply 1 of this device fulfils EN/IEC 61000-3-12, provided that the short-cir-
cuit power S
at the transfer point of the energy provider to the operator is greater
k
than or equal to 1200 kW. The installer or operator of the device is, therefore,
responsible for ensuring, in case a consultation with the EVU is needed, that the
device is only connected, if the short-circuit power S
1200 kW.
● Mains supply 1 of the device fulfils ICE/ EN 61000-3-11 and is to be connected to
a suitable voltage source, which has a current rating ≥100 A per phase. Connect
to the EVU to ensure that the current rating at the transfer point is sufficient for the
device.
● Mains supply 2 of this device fulfils EN/ IEC 61000-3-12.
● The main supply 2 of this device fulfills IEC/EN 61000-3-11 and is to be connected
to a suitable voltage source, whose maximum allowed system impedance at the
interface is Z
= 0.257 Ω. Connect to the EVU to ensure that the mains supply 2
max
is only connected to a grid with the maximum of this impedance.
Planning
is greater than or equal to
k
is greater than or equal to
k
115