Wireless mesh 2,4 ghz
Table of Contents

Advertisement

Parameter name
Address of register
cloned from WTR, slot
7
Address of register
cloned from WTR, slot
8
Address of register
cloned from WTR, slot
9
Address of register
cloned from WTR, slot
10
Parameter value
Temperature
Humidity
Transmitter specific
measurement 1...3
Input 1...4
Battery level
Signal strength

4.4 Configuring Value Over Bus settings

You can configure up to three Value Over bus functions.
1. Press the Value Over Bus button in the Configurations view.
2. Select the configuration you are going to set by pressing the number.
3. Make the settings.
See the chapter
4. Press the Confirm changes button to save the changes.
5. Press Install to device button to write the changes to the device.

4.4.1 Available settings for value over bus

Parameter name
Bus mode
Bus value type

4.5 Configuring communication settings

1. Press the Communication button in the Configurations display.
2. Make the settings.
See the chapter
3. Press the Confirm changes button to save the changes.
4. Press Install to device button to write the changes to the device.
Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | fax. +358 5 230 9210 | info@produal.com
Published: 18.07.2019
Values
Default
See the
Input 3
following table.
See the
Input 4
following table.
See the
Battery level
following table.
See the
Signal strength
following table.
Description
Temperature measurement.
Humidity measurement.
Transmitter specific measurements (e.g. Transmitter specific value 1 = CO
measurement).
Inputs' values.
Transmitter battery level.
Transmitter signal strength.
Available settings for value over bus
Values
Default
Global type and
Global type and
value / Global type,
value
individual values
No value /
No value
Temperature / ...
Available settings for communication
Information is subject to change without prior notice.
Description
The transmitters' value to be cloned to slot 7.
The values are cloned to base unit registers
18600...18699.
The transmitters' value to be cloned to slot 8.
The values are cloned to base unit registers
18700...18799.
The transmitters' value to be cloned to slot 9.
The values are cloned to base unit registers
18800...18899.
The transmitters' value to be cloned to slot 10.
The values are cloned to base unit registers
18900...18999.
on page 24 for more details.
Description
Alarm for offline transmitters. Set the offline time
that activates the alarm.
See the available values and their descriptions
from the chapter
Available value over bus (VOB)