Configuring Input Register Cloning; Available Settings For Input Register Cloning - Produal Proxima WBU Commissioning And Maintenance Instructions

Wireless mesh 2,4 ghz
Table of Contents

Advertisement

Parameter name
Battery alarm limit
General temperature
alarm, low
General temperature
alarm, high
General RH% alarm,
low
General RH% alarm,
high
General CO2 alarm,
low
General CO2 alarm,
high

4.3 Configuring input register cloning

1. Press the WTR Input Register Cloning button in the Configurations view.
2. Make the settings.
See the chapter
3. Press the Confirm changes button to save the changes.
4. Press Install to device button to write the changes to the device.

4.3.1 Available settings for input register cloning

Parameter name
Address of register
cloned from WTR, slot
1
Address of register
cloned from WTR, slot
2
Address of register
cloned from WTR, slot
3
Address of register
cloned from WTR, slot
4
Address of register
cloned from WTR, slot
5
Address of register
cloned from WTR, slot
6
Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | fax. +358 5 230 9210 | info@produal.com
Published: 18.07.2019
Values
Default
50...100 %
11 %
Off /
Off
-100,0...100,0 °C
Off /
Off
-100,0...100,0 °C
Off /
Off
0,00...100,00 %rH
Off /
Off
0,00...100,00 %rH
Off /
Off
0...10000 ppm
Off /
Off
0...10000 ppm
Available settings for input register cloning
Values
Default
See the
Temperature
following table.
See the
Humidity
following table.
See the
Transmitter
following table.
specific
measurement 1
See the
Transmitter
following table.
specific
measurement 2
See the
Input 1
following table.
See the
Input 2
following table.
Information is subject to change without prior notice.
Description
Battery level alarm. Set the battery level that
activates the alarm.
Note: The alarm activates when the
level drops under the set value. For
example, 11 % means that the alarm
activates when the battery level is
10 %.
Low temperature alarm. Alarm activates when
any transmitter's temperature drops below the set
value.
High temperature alarm. Alarm activates when any
transmitter's temperature rises over the set value.
Low humidity alarm. Alarm activates when any
transmitter's humidity level drops below the set
value.
High humidity alarm. Alarm activates when any
transmitter's humidity level rises over the set
value.
Low CO
alarm. Alarm activates when any
2
transmitter's CO
level drops below the set value.
2
High CO
alarm. Alarm activates when any
2
transmitter's CO
level rises over the set value.
2
on page 23 for more details.
Description
The transmitters' value to be cloned to slot 1.
The values are cloned to base unit registers
18000...18099.
The transmitters' value to be cloned to slot 2.
The values are cloned to base unit registers
18100...18199.
The transmitters' value to be cloned to slot 3.
The values are cloned to base unit registers
18200...18299.
The transmitters' value to be cloned to slot 4.
The values are cloned to base unit registers
18300...18399.
The transmitters' value to be cloned to slot 5.
The values are cloned to base unit registers
18400...18499.
The transmitters' value to be cloned to slot 6.
The values are cloned to base unit registers
18500...18599.
23 (63)
EN - 5401comm