Modbus Interface - AUMA SGExC 05.1 Operation Instructions Manual

Part-turn, control unit: electromechanic with actuator controls
Hide thumbs Also See for SGExC 05.1:
Table of Contents

Advertisement

SGExC 05.1
SGExC 12.1 Control unit: electromechanic
ACExC 01.2 Intrusive Modbus RTU
Electrical connection
Overvoltage protection (option)
Wiring diagram
1)
The reversing contactors are designed for a lifetime of 2 million starts.
2)
For the assignment of AUMA power classes, please refer to electrical data on actuator.
3)
All input signals must be supplied with the same potential.
4)
Not possible in combination with PTC tripping device
5)
In combination with plug/socket connector KPH only
12.3

Modbus interface

Settings/programming the Modbus interface
Setting the Modbus interface
Commands and signals of the fieldbus interface
Process representation output
(command signals)
Process representation input
(feedback signals)
Process representation input
(fault signals)
Behaviour on loss of communi-
cation
1)
Requires magnetic limit and torque transmitter (MWG) in actuator
General fieldbus interface data
Communication protocol
Network topology
Transmission medium
Fieldbus interface
Standard:
Plug/socket connector with screw-type terminals (KP, KPH) Ex e (increased safety) and M-
threads
Options:
Plug/socket connector with terminal blocks (KES) Ex e (increased safety)
Plug/socket connector with terminal blocks (KES) Ex d (flameproof enclosure)
Pg-threads, NPT-threads, G-threads, special threads
Parking frame for wall mounting of the disconnected plug
Protection cover for plug compartment (when plug is removed)
Protection of the actuator and control electronics against overvoltages on the fieldbus cables
5)
of up to 4 kV
Refer to name plate
Baud rate, parity and Modbus address are set via the display of the AUMATIC
OPEN, STOP, CLOSE, position setpoint, RESET, EMERGENCY operation command, enable
LOCAL, Interlock OPEN/CLOSE
End position OPEN, CLOSED
Actual position value
1)
Actual torque value
Selector switch in position LOCAL/REMOTE
Running indication (directional)
Torque switch OPEN, CLOSED
Limit switch OPEN, CLOSED
Manual operation by handwheel or via local controls
2 analogue and 4 digital customer inputs
Motor protection tripped
Torque switch tripped in mid-travel
One phase missing
Loss of the analogue customer inputs
The behaviour of the actuator is programmable:
Stop in current position
Travel to end position OPEN or CLOSED
Travel to any intermediate position
Execute last received operation command
Modbus RTU according to IEC 61158 and IEC 61784
Line (bus) structure. When using repeaters, tree structures can also be implemented.
Coupling and uncoupling of devices during operation without affecting other devices is
possible.
Twisted, screened copper cable according to IEC 61158
EIA-485 (RS485)
Technical data